EPR/PVC Power Cable with Copper Tape Shield (15kV)
EPR/PVC Power Cable with Copper Tape Shield (15kV)
UL Type MV-105, 133% Ins. Level, 220 Mils, 15kV
Product Approvals:
-
Industry Approvals
-
National Electric Code (NEC)
-
UL 1072
-
ICEA S-93-639/NEMA WC74
-
ICEA S-97-682
-
AEIC CS8
-
UL Listed as Type MV-105 for use in accordance with NEC
-
Sizes 1/0 AWG and larger are listed and marked "Sunlight-Resistant FOR CT USE" i naccordance with NEC
-
IEEE 1202 (70,000 BTU/hr)/CSA FT4
-
Meets EPA 40 CFR, Part 2671 for leachable lead content per TLCP method
-
OSHA acceptable
-
Optional Flame Tests:
-
ICEA T-29-520 (210,000 BTU/hr)
EPR/PVC Power Cable with Copper Tape Shield (15kV) Construction:
-
Conductor:
-
2 AWG thru 1000 kcmil annealed bare copper compact Class B strand
-
Extended Strand Shield (ESS):
-
Extruded Thermoset Semi-Conducting Stress Control Layer over conductor
-
Insulation:
-
Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers
-
Extruded Insulation Shield (EIS):
Thermoset Semi-Conducting Polymeric Layer free stripping from insulation
-
Metallic Shield
-
5 mil annealed copper tape with an overlap of 25%
-
Jacket:
-
Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)
EPR/PVC Power Cable with Copper Tape Shield (15kV) Options:
-
PVC jacket color other than black
-
Flame Retardant, Chlorinated Polyethylene (CPE) jacket
-
Low-Smoke, Halogen-Free (LSZH) jacket
-
STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-0-610
-
100% insulation level
EPR/PVC Power Cable with Copper Tape Shield (15kV) Applications:
-
Installed in a broad range of commercial, industrial and utility projects such as pulp and paper mills, petrochemical plants, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines and fossil fuel utility generating stations
-
Suitable for use in wet or dry locations, when installed in accordance with NEC
-
For use in aerial, direct burial, conduit, open tray and underground duct installations
-
For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)
EPR/PVC Power Cable with Copper Tape Shield (15kV) Features:
-
Rated at 105°C
-
Excellent heat and moisture resistance
-
Excellent flame resistance
-
Outstanding corona resistance
-
Flexibility for easy handling
-
High dielectric strength
-
Low moisture absorption
-
Electrical stability under stress
-
Low dielectric loss
-
Chemical resistant
-
Meets cold bend test at -35°C
Click on the part numbers below for more detailed specs, to buy online* or to submit a RFQ for large quantity discounts and/or customization.   *Not available on all products.
|
Part Number
|
AWG Size
|
Jacket Thick
|
Nom. O.D. (in)
|
Nom. Dia. of Cond.
|
Min. Insul. Dia. (in)
|
Max. Insul. Dia. (in)
|
Approx LBS/MFT
|
Ampacity (Duct in Air)
|
Ampacity (Underground)
|
Ampacity (Tray)
|
|
85155.065100-18
|
2
|
0.080
|
0.99
|
0.27
|
0.710
|
0.800
|
658
|
165
|
165
|
|
|
85155.065050-18
|
1
|
0.080
|
1.02
|
0.31
|
0.745
|
0.830
|
733
|
190
|
185
|
|
|
85155.067550-18
|
1/0
|
0.080
|
1.06
|
0.34
|
0.780
|
0.865
|
825
|
215
|
215
|
220
|
|
85155.067600-18
|
2/0
|
0.080
|
1.10
|
0.38
|
0.820
|
0.905
|
938
|
255
|
245
|
250
|
|
85155.067650-18
|
3/0
|
0.080
|
1.14
|
0.43
|
0.865
|
0.955
|
1078
|
290
|
275
|
290
|
|
85155.067700-18
|
4/0
|
0.080
|
1.21
|
0.48
|
0.920
|
1.005
|
1261
|
330
|
315
|
335
|
|
85155.068000-18
|
250
|
0.080
|
1.25
|
0.53
|
0.970
|
1.060
|
1407
|
265
|
245
|
270
|
|
85155.068100-18
|
350
|
0.080
|
1.35
|
0.62
|
1.070
|
1.155
|
1783
|
440
|
415
|
460
|
|
85155.068250-18
|
500
|
0.080
|
1.47
|
0.74
|
1.190
|
1.275
|
2331
|
535
|
500
|
575
|
|
85155.068500-18
|
750
|
0.080
|
1.65
|
0.91
|
1.370
|
1.460
|
3234
|
655
|
610
|
745
|
|
85155.068750-18
|
1000
|
0.110
|
1.86
|
1.06
|
1.520
|
1.610
|
4219
|
755
|
690
|
890
|