EPR/HYP Unshielded Power Cable (2400 V)

EPR/HYP Unshielded Power Cable (2400 V)
UL Type MV-90, 600 V

We're sorry, but this cable is no longer available. Please call us at 800-472-4655 or email us and we will help you find a suitable alternative.

Product Approvals:

  • National Electric Code (NEC)
  • ICEA S-96-659/NEMA WC71
  • UL 1072
  • FAA L824 specification for cable for Underground Airport Lighting Circuits
  • UL Listed as Type MV-90 for use in accordance with NEC
  • Sizes 1/0 AWG and larger are listed and marked "Sunlight-Resistant FOR CT USE" in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr)
  • Listed "oil-resistant II"
  • Meets EPA 40 CFR part 261 leachable lead content per TCLP method
  • OSHA acceptable

EPR/HYP Unshielded Power Cable (2400 V) Construction:

  • Conductor:
    • 9 AWG thru 1000 kcmil annealed bare copper Class B strand
  • Extended Strand Shield (ESS):
    • Extruded Thermoset Semi-Conducting Stress Control Layer over conductor
  • Insulation:
    • Ethylene Propylene Rubber (EPR) colored to contrast with black jacket material
  • Jacket:
    • Low-Lead Chlorosulfonated Polyethylene (CSPE)/Elastomer blend

EPR/HYP Unshielded Power Cable (2400 V) Options:

  • Multi conductor constructions
  • Other constructions available upon request

EPR/HYP Unshielded Power Cable (2400 V) Applications:

  • For use in industrial and utility applications, where ease of installation is a major concern because of limited space and exposure to personnel is minimal
  • For use in wet or dry locations, when installed in accordance with NEC
  • For use in aerial, conduit, open tray and underground duct installations

EPR/HYP Unshielded Power Cable (2400 V) Features:

  • Rated at 90°C
  • Excellent heat and moisture resistance
  • Flexibility for easy handling
  • High dielectric strength
  • Low moisture absorption
  • Electrical stability under stress
  • Low dielectric loss
  • Chemical and radiation resistant
  • Simplifies splicing and termination because there is no need to handle the cable shield
  • Extra-tough, mechanically rugged composite insulation and jacket construction
  • Meets cold bend test at -35°C

 

Part Number Nom. O.D. (in)Approx LBS/MFTAWG SizeNom. Insul. Thick. (in)Nom. Dia. of Cond.Min. Insul. Dia. (in)
74505.205400-18 0.58 196 8 0.125 0.14 0.41
74505.205300-18 0.62 241 6 0.125 0.17 0.44
74505.205200-18 0.66 308 4 0.125 0.22 0.49
74505.205100-18 0.72 408 2 0.125 0.27 0.55
74505.205050-18 0.76 476 1 0.125 0.31 0.58
74505.207550-18 0.79 562 1/0 0.125 0.34 0.62
74505.207600-18 0.84 666 2/0 0.125 0.38 0.66
74505.207650-18 0.92 823 3/0 0.125 0.43 0.71
74505.207700-18 0.97 983 4/0 0.125 0.48 0.76
74505.208000-18 1.08 1183 250 0.140 0.53 0.84
74505.208100-18 1.17 1545 350 0.140 0.62 0.93
74505.208250-18 1.30 2077 500 0.140 0.74 1.06
74505.208500-18 1.24 3040 750 0.155 0.91 1.26
74505.208750-18 1.70 3913 1000 0.155 1.06 1.42