Four Conductor XLPE/PVC/AIA/PVC Armored Control Cable (1000 V)

CSA TECK90 Armored Control Cable (1000 V)

XLPE/PVC/AIA/PVC Four Conductor Armored Control and Power Cable
1000 V, CSA TECK90

Product Approvals:

  • CSA Standard C22.2 No. 131 and No. 174
  • CSA Approval number: LR1781
  • CSA FT1 and FT4
  • IEEE 383 (70,000 BTU/hr)
  • UL 1581 (70,000 BTU/hr)
  • IEEE 1202 (70,000 BTU/hr) CSA FT4
  • ICEA T-30-520 (70,000 BTU/hr)
  • Hazardous Location Rating: HL
  • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method
  • OSHA acceptable

Four Conductor TECK90 Armored Control Cable (1000 V) Construction:

  • Conductor
    • 14 AWG thru 8 AWG bare copper Class B compressed concentric round to ASTM B8
    • 6 AWG thru 1000 kcmil bare copper compact Class B strand
  • Ground (Bonding) Conductor:
    • The conductor consists of one uninsulated stranded bare copper conductor
  • Insulation:
    • Cross-linked Polyethylene (XLPE) Type RW90
    • Color-coded: 14 AWG to 2 AWG-black and white; 1 AWG to 1000 kcmil-printed numbers
  • Inner Jacket:
    • Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
  • Armor:
    • Aluminum Interlocked Armor (AIA)
  • Overall Jacket:
    • ACID-FLAME CHECK flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black

Four Conductor TECK90 Armored Control Cable (1000 V) Applications:

  • For exposed and concealed wiring in dry, damp or wet locations
  • For use in ventilated, non-ventilated and ladder-type cable trays in dry, damp or wet locations
  • For direct earth burial (with protection as required by inspection authority)
  • For wiring in all hazardous locations when used with certified HL cable glands

Four Conductor TECK90 Armored Control Cable (1000 V) Features:

  • Rated at 90°C wet or dry
  • Excellent crush, oil and chemical resistance
  • Provides long service life
  • Meets cold bend and impact tests at -40°C
Part Number AWG SizeNo. of Cond.Nom. Insul. Thick. (in)Nom. O.D. of Cable (in)Approx LBS/MFTArmor (in)Ampacity @ 30°CGround AWG Size
160970-18 14 4 0.045 0.80 290 0.72 15 14
396590-18 12 4 0.045 0.88 357 0.79 20 14
396580-18 10 4 0.045 0.93 455 0.85 30 12
165625-18 8 4 0.045 1.00 548 0.92 45 10
5644.0153-18 6 4 0.060 1.25 907 1.15 65 8
5644.0102-18 4 4 0.060 1.35 1168 1.26 85 8
5644.01015-18 3 4 0.060 1.40 1373 1.31 105 6
5644.0101-18 2 4 0.060 1.46 1583 1.37 120 6
5644.02005-18 1 4 0.080 1.72 2032 1.60 140 6
5644.01255-18 1/0 4 0.080 1.81 2365 1.69 155 6
5644.0126-18 2/0 4 0.080 1.91 2745 1.79 185 6
5644.01265-18 3/0 4 0.080 2.03 3398 1.91 210 4
5644.0227-18 4/0 4 0.080 2.21 4170 2.09 235 4
5644.023-18 250 4 0.090 2.35 4789 2.23 265 4
5644.0131-18 350 4 0.090 2.60 6307 2.46 325 3
5644.01825-18 500 4 0.090 2.90 8438 2.76 395 3
5644.0285-18 750 4 0.090 3.42 12411 3.24 500 2
5644.01875-18 1000 4 0.090 3.84 15800 3.65 585 1