Shielded Plenum Fire Alarm Cable (NEC Type FPLP, PVC Jacket)

16 AWG FPLP Shielded Plenum Fire Alarm Cable

Shielded Plenum Fire Alarm Cable Sample: FPLP-16-2C-S

Plenum NEC Type FPLP Shielded Fire Alarm Cable

FPLP Alarm Cable Compliances:

  • NEC Article 760
  • UL Type FPLP (UL: 75°C, 300V)
  • California State Fire Marshall Approved
  • Designed to meet NFPA 262 and CSA FT-6 Steiner Tunnel Fire Tests for Plenum Applications

FPLP Alarm Cable Construction:

  • Conductor:
    • Solid Bare Copper, Fully Annealed per ASTM B3
  • Insulation:
  • Shielding:
    • Overall Polyester Supported Aluminum Foil
    • Stranded Tinned Copper Drain Wire
  • Jacket:
    • Red Premium-Grade PVC
    • Temperature Range: 0°C to +75°C
    • Sequential footage markings to facilitate installation
    • Includes ripcord

FPLP Alarm Cable Applications:

  • Wiring of fire alarms
  • Smoke detectors
  • Voice communications
  • Burglar Alarms
  • Fire protective circuits
  • Suggested voltage rating: 300 Volts
Part Number AWG SizeNo. of Cond.Conductor StrandingNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)
7084 22 2 Solid 0.010 0.015 0.126
7204 18 2 Solid 0.010 0.015 0.158
7206 18 3 Solid 0.010 0.015 0.165
7208 18 4 Solid 0.010 0.015 0.183
7212 18 6 Solid 0.010 0.015 0.216
7224 16 2 Solid 0.010 0.015 0.180
7228 16 4 Solid 0.010 0.015 0.210
7244 14 2 Solid 0.012 0.015 0.210
7248 14 4 Solid 0.012 0.015 0.248
7264 12 2 Solid 0.012 0.015 0.252
7268 12 4 Solid 0.012 0.015 0.300