add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 

Single Conductor XLPE/PVC/AIA/PVC Armored Control Cable (1000 V)

CSA TECK90 Armored Control Cable (1000 V)


XLPE/PVC/AIA/PVC Single Conductor Armored Control and Power Cable
1000 V, CSA TECK90

Product Approvals:

  • CSA Standard C22.2 No. 131 and No. 174
  • CSA Approval number: LR1781
  • CSA FT1 and FT4
  • IEEE 383 (70,000 BTU/hr)
  • UL 1581 (70,000 BTU/hr
  • IEEE 1202 (70,000 BTU/hr) CSA FT4
  • ICEA T-30-520 (70,000 BTU/hr)
  • Hazardous Location Rating: HL
  • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method
  • OSHA acceptable

Single Conductor TECK90 Armored Control Cable (1000 V) Construction:

  • Conductor: 6 AWG thru 1000 kcmil bare copper compact Class B strand
  • Ground (Bonding) Conductor: The conductor is a concentric serving of solid bare copper wires applied over the insulation
  • Insulation: Cross-linked Polyethylene (XLPE) Type RW90; Black
  • Inner Jacket: Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
  • Armor: Aluminum Interlocked Armor (AIA)
  • Overall Jacket: ACID-FLAME CHECK flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black

Single Conductor TECK90 Armored Control Cable (1000 V) Applications:

  • For exposed and concealed wiring in dry, damp or wet locations
  • For use in ventilated, non-ventilated and ladder-type cable trays in dry, damp or wet locations
  • For direct earth burial (with protection as required by inspection authority)
  • For wiring in all hazardous locations when used with certified HL cable glands

Single Conductor TECK90 Armored Control Cable (1000 V) Features:

  • Rated at 90°C wet or dry
  • Excellent crush, oil and chemical resistance
  • Provides long service life
  • Cost-effective alternative to installations in conduit
  • Meets cold bend and impact tests at -40°C
Part Number AWG SizeApprox LBS/MFTNom. Insul. Thick. (in)Nom. O.D. (in)Armor (in)Ampacity @ 30°CGround AWG Size
5644.0203-18 6 320 0.060 0.7700 0.68 100 8
5644.0252-18 4 410 0.060 0.8100 0.73 135 6
5644.01515-18 3 450 0.060 0.8400 0.76 155 6
5644.0251-18 2 510 0.060 0.8700 0.78 180 6
5644.02505-18 1 680 0.080 0.9600 0.88 210 4
5644.01755-18 1/0 760 0.080 1.0000 0.91 245 4
5644.0176-18 2/0 860 0.080 1.0400 0.95 285 4
5644.01765-18 3/0 1080 0.080 1.1200 1.03 330 3
5644.0127-18 4/0 1270 0.080 1.1700 1.08 385 3
5644.013-18 250 1490 0.090 1.2900 1.21 425 2
5644.0181-18 350 1910 0.090 1.3900 1.30 530 1
5644.01325-18 500 2510 0.090 1.5100 1.42 660 1/0
5644.0135-18 750 3510 0.090 1.6900 1.59 845 2/0
5644.01375-18 1000 4430 0.090 1.9000 1.81 1000 2/0