Unshielded Multi-Conductor Type TC Tray Cable (600 V)

TRAY 10-2-FL

Sample Shown: TRAY 10-2-FL

    TYPE TC TRAY CABLE
    CONTROL / INSTRUMENTATION CABLE
    VNTC / UL Type TC / TC-ER Rated
    600 VOLTS
    90°C DRY/75°C WET
    PVC/Nylon Insulation with Overall PVC Jacket

    Type TC Tray Cable:
    This specification covers multi-conductor cables having VW-1 TFN or THHN/THWN (PVC/Nylon) conductors with an overall polyvinyl chloride(PVC) jacket, conforming to Article 318 “Cable Trays” and Article 340 “Power and Control Cable Type TC” of the National Electrical Code, and Standard 1277 of Underwriters Laboratories, Inc. Meets the requirements of ICEA T-29-520 and T-30-520 flame tests as well as the 70,000 BTU “Cable Tray Propagation Test” per IEEE-383. Rated 600 volts, 90°C dry and 75°C wet.

    Type TC Tray Cable Applications:

    • Control circuits for operation and interconnection of protective and signaling devices, and for general use in manufacturing, industrial and commercial distribution systems
    • For installation in cable trays, raceways, conduit, aerial (when supported with a messenger) and for direct burial
    • In hazardous locations per NEC Article 501, Class 1 Division 2.
    • May be used in wet or dry locations; is sunlight and weather  resistant; excellent abrasion and chemical resistance

    Type TC Tray Cable Construction:

    • Type TC Tray Cable Conductors: Stranded bare copper, Class B per UL 62 (*Parts are also available with tinned copper conductors)
    • Type TC Tray Cable Insulation:
      • 16/18 AWG - Extruded PVC with Nylon Jacket (.004” thickness) Type TFFN per UL 66
      • 10/12/14 AWG - Extruded PVC with Nylon Jacket (.004” thickness; 10 AWG has .005”), Type THHN/THWN per UL 83
    • Type TC Tray Cable Overall Jacket: Black PVC (sunlight resistant and flame retardant) per UL 1277 requirements for Type TC power and control cables
    • Type TC Tray Cable Assembly: Conductors are cabled with fillers where needed to make a round, compact core. Suitable tape is applied over construction. FL stands for Flat Construction, which is available on 2 conductor cables.
    • Type TC Tray Cable Color Coding:
      ICEA Method 1-E2 Table K-2

    Type TC Tray Cable Standards:

    • UL  1277 Type TC-ER (Extended Run, -ER Rated is for 3 conductors or more only)
    • NEC Article 336
    • Passes IEEE 383 Flame Test (70,000 BTU/hr)
    • UL Subject 1277 (70,000 BTU/hr)

     

    Part Number AWG SizeNo. of Cond.Conductor StrandingNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)Approx LBS/MFT
    TRAY 18-2-FL 18 2 7 0.015 0.045 0.181 x 0.268 33
    TRAY 18-2 18 2 7/.0152 0.015 0.045 0.270 36
    TRAY 18-3 18 3 7 0.015 0.045 0.281 45
    TRAY 18-4 18 4 7 0.015 0.045 0.304 55
    TRAY 18-5 18 5 7 0.015 0.045 0.328 65
    TRAY 18-6 18 6 7 0.015 0.045 0.370 80
    TRAY 18-7 18 7 7 0.015 0.045 0.354 84
    TRAY 18-9 18 9 7 0.015 0.045 0.408 105
    TRAY 18-12 18 12 7 0.015 0.045 0.454 133
    TRAY 18-15 18 15 7 0.015 0.045 0.532 176
    TRAY 18-19 18 19 7 0.015 0.060 0.558 211
    TRAY 18-25 18 25 7 0.015 0.060 0.655 266
    TRAY 18-30 18 30 7 0.015 0.060 0.695 310
    TRAY 18-37 18 37 7 0.015 0.060 0.745 382
    TRAY 16-2-FL 16 2 7 0.015 0.045 0.193 x 0.292 42
    TRAY 16-2 16 2 7/.0192 0.015 0.045 0.294 45
    TRAY-16-3 16 3 7 0.015 0.045 0.308 55
    TRAY 16-4 16 4 7 0.015 0.045 0.334 71
    TRAY 16-5 16 5 7 0.015 0.045 0.361 85
    TRAY 16-6 16 6 7 0.015 0.045 0.390 109
    TRAY 16-7 16 7 7 0.015 0.045 0.391 112
    TRAY 16-9 16 9 7 0.015 0.045 0.452 140
    TRAY 16-12 16 12 7 0.015 0.045 0.535 188
    TRAY 16-15 16 15 7 0.015 0.060 0.589 235
    TRAY 16-19 16 19 7 0.015 0.060 0.619 284
    TRAY 16-25 16 25 7 0.015 0.060 0.718 365
    TRAY 16-30 16 30 7 0.015 0.060 0.759 425
    TRAY 16-37 16 37 7 0.015 0.080 0.857 545
    TRAY 14-2-FL 14 2 7 0.015 0.045 0.206 x 0.318 55
    TRAY 14-2 14 2 7/.0242 0.015 0.045 0.340 77
    TRAY 14-3 14 3 7 0.015 0.045 0.337 77
    TRAY 14-4 14 4 7 0.015 0.045 0.366 97
    TRAY 14-5 14 5 7 0.015 0.045 0.397 116
    TRAY 14-7 14 7 7 0.015 0.045 0.431 155
    TRAY 14-9 14 9 7 0.015 0.060 0.531 211
    TRAY 14-12 14 12 7 0.015 0.060 0.590 270
    TRAY 14-15 14 15 7 0.015 0.060 0.652 328
    TRAY 14-19 14 19 7 0.015 0.080 0.686 401
    TRAY 14-25 14 25 7 0.015 0.080 0.838 549
    TRAY 14-30 14 30 7 0.015 0.080 0.884 642
    TRAY 14-37 14 37 7 0.015 0.080 0.951 773
    TRAY 12-2-FL 12 2 7 0.015 0.045 0.228 x 0.363 76
    TRAY 12-2 12 2 7 0.015 0.045 0.362 80
    TRAY 12-3 12 3 7 0.015 0.045 0.383 108
    TRAY 12-4 12 4 7 0.015 0.045 0.418 137
    TRAY 12-5 12 5 7 0.015 0.045 0.456 166
    TRAY 12-7 12 7 7 0.015 0.045 0.496 224
    TRAY 12-9 12 9 7 0.015 0.060 0.609 301
    TRAY 12-12 12 12 7 0.015 0.060 0.680 388
    TRAY 12-15 12 15 7 0.015 0.060 0.754 475
    TRAY 12-19 12 19 7 0.015 0.060 0.834 619
    TRAY 12-25 12 25 7 0.015 0.080 0.985 775
    TRAY 12-30 12 30 7 0.015 0.080 1.023 937
    TRAY 12-37 12 37 7 0.015 0.080 1.102 1133
    TRAY 10-2-FL 10 2 7 0.015 0.045 0.262 x 0.430 109
    TRAY 10-2 10 2 7/.0385 0.020 0.045 0.428 115
    TRAY 10-3 10 3 7 0.015 0.045 0.457 157
    TRAY 10-4 10 4 7 0.015 0.045 0.501 202
    TRAY 10-5 10 5 7 0.015 0.060 0.578 261
    TRAY 10-7 10 7 7 0.015 0.060 0.628 352
    TRAY 10-9 10 9 7 0.015 0.060 0.732 445
    TRAY 10-12 10 12 7 0.015 0.080 0.861 610
    TRAY 10-19 10 19 7 0.015 0.080 1.020 1060