add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 

Unshielded Multi-Conductor Type TC Tray Cable (600 V)

TRAY 10-2-FL

Sample Shown: TRAY 10-2-FL

TYPE TC TRAY CABLE
CONTROL / INSTRUMENTATION CABLE
VNTC / UL Type TC / TC-ER Rated
600 VOLTS
90°C DRY/75°C WET
PVC/Nylon Insulation with Overall PVC Jacket

Type TC Tray Cable:
This specification covers multi-conductor cables having VW-1 TFN or THHN/THWN (PVC/Nylon) conductors with an overall polyvinyl chloride(PVC) jacket, conforming to Article 318 “Cable Trays” and Article 340 “Power and Control Cable Type TC” of the National Electrical Code, and Standard 1277 of Underwriters Laboratories, Inc. Meets the requirements of ICEA T-29-520 and T-30-520 flame tests as well as the 70,000 BTU “Cable Tray Propagation Test” per IEEE-383. Rated 600 volts, 90°C dry and 75°C wet.

Type TC Tray Cable Applications:

  • Control circuits for operation and interconnection of protective and signaling devices, and for general use in manufacturing, industrial and commercial distribution systems
  • For installation in cable trays, raceways, conduit, aerial (when supported with a messenger) and for direct burial
  • In hazardous locations per NEC Article 501, Class 1 Division 2.
  • May be used in wet or dry locations; is sunlight and weather  resistant; excellent abrasion and chemical resistance

Type TC Tray Cable Construction:

  • Type TC Tray Cable Conductors: Stranded bare copper, Class B per UL 62 (*Parts are also available with tinned copper conductors)
  • Type TC Tray Cable Insulation:
    • 16/18 AWG - Extruded PVC with Nylon Jacket (.004” thickness) Type TFFN per UL 66
    • 10/12/14 AWG - Extruded PVC with Nylon Jacket (.004” thickness; 10 AWG has .005”), Type THHN/THWN per UL 83
  • Type TC Tray Cable Overall Jacket: Black PVC (sunlight resistant and flame retardant) per UL 1277 requirements for Type TC power and control cables
  • Type TC Tray Cable Assembly: Conductors are cabled with fillers where needed to make a round, compact core. Suitable tape is applied over construction. FL stands for Flat Construction, which is available on 2 conductor cables.
  • Type TC Tray Cable Color Coding:
    ICEA Method 1-E2 Table K-2

Type TC Tray Cable Standards:

  • UL  1277 Type TC-ER (Extended Run, -ER Rated is for 3 conductors or more only)
  • NEC Article 336
  • Passes IEEE 383 Flame Test (70,000 BTU/hr)
  • UL Subject 1277 (70,000 BTU/hr)

 

Part Number AWG SizeNo. of Cond.Conductor StrandingNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)Approx LBS/MFT
TRAY 18-2-FL 18 2 7 0.015 0.045 0.181 x 0.268 33
TRAY 18-2 18 2 7/.0152 0.015 0.045 0.270 36
TRAY 18-3 18 3 7 0.015 0.045 0.281 45
TRAY 18-4 18 4 7 0.015 0.045 0.304 55
TRAY 18-5 18 5 7 0.015 0.045 0.328 65
TRAY 18-6 18 6 7 0.015 0.045 0.370 80
TRAY 18-7 18 7 7 0.015 0.045 0.354 84
TRAY 18-9 18 9 7 0.015 0.045 0.408 105
TRAY 18-12 18 12 7 0.015 0.045 0.454 133
TRAY 18-15 18 15 7 0.015 0.045 0.532 176
TRAY 18-19 18 19 7 0.015 0.060 0.558 211
TRAY 18-25 18 25 7 0.015 0.060 0.655 266
TRAY 18-30 18 30 7 0.015 0.060 0.695 310
TRAY 18-37 18 37 7 0.015 0.060 0.745 382
TRAY 16-2-FL 16 2 7 0.015 0.045 0.193 x 0.292 42
TRAY 16-2 16 2 7/.0192 0.015 0.045 0.294 45
TRAY-16-3 16 3 7 0.015 0.045 0.308 55
TRAY 16-4 16 4 7 0.015 0.045 0.334 71
TRAY 16-5 16 5 7 0.015 0.045 0.361 85
TRAY 16-6 16 6 7 0.015 0.045 0.390 109
TRAY 16-7 16 7 7 0.015 0.045 0.391 112
TRAY 16-9 16 9 7 0.015 0.045 0.452 140
TRAY 16-12 16 12 7 0.015 0.045 0.535 188
TRAY 16-15 16 15 7 0.015 0.060 0.589 235
TRAY 16-19 16 19 7 0.015 0.060 0.619 284
TRAY 16-25 16 25 7 0.015 0.060 0.718 365
TRAY 16-30 16 30 7 0.015 0.060 0.759 425
TRAY 16-37 16 37 7 0.015 0.080 0.857 545
TRAY 14-2-FL 14 2 7 0.015 0.045 0.206 x 0.318 55
TRAY 14-2 14 2 7/.0242 0.015 0.045 0.340 77
TRAY 14-3 14 3 7 0.015 0.045 0.337 77
TRAY 14-4 14 4 7 0.015 0.045 0.366 97
TRAY 14-5 14 5 7 0.015 0.045 0.397 116
TRAY 14-7 14 7 7 0.015 0.045 0.431 155
TRAY 14-9 14 9 7 0.015 0.060 0.531 211
TRAY 14-12 14 12 7 0.015 0.060 0.590 270
TRAY 14-15 14 15 7 0.015 0.060 0.652 328
TRAY 14-19 14 19 7 0.015 0.080 0.686 401
TRAY 14-25 14 25 7 0.015 0.080 0.838 549
TRAY 14-30 14 30 7 0.015 0.080 0.884 642
TRAY 14-37 14 37 7 0.015 0.080 0.951 773
TRAY 12-2-FL 12 2 7 0.015 0.045 0.228 x 0.363 76
TRAY 12-2 12 2 7 0.015 0.045 0.362 80
TRAY 12-3 12 3 7 0.015 0.045 0.383 108
TRAY 12-4 12 4 7 0.015 0.045 0.418 137
TRAY 12-5 12 5 7 0.015 0.045 0.456 166
TRAY 12-7 12 7 7 0.015 0.045 0.496 224
TRAY 12-9 12 9 7 0.015 0.060 0.609 301
TRAY 12-12 12 12 7 0.015 0.060 0.680 388
TRAY 12-15 12 15 7 0.015 0.060 0.754 475
TRAY 12-19 12 19 7 0.015 0.060 0.834 619
TRAY 12-25 12 25 7 0.015 0.080 0.985 775
TRAY 12-30 12 30 7 0.015 0.080 1.023 937
TRAY 12-37 12 37 7 0.015 0.080 1.102 1133
TRAY 10-2-FL 10 2 7 0.015 0.045 0.262 x 0.430 109
TRAY 10-2 10 2 7/.0385 0.020 0.045 0.428 115
TRAY 10-3 10 3 7 0.015 0.045 0.457 157
TRAY 10-4 10 4 7 0.015 0.045 0.501 202
TRAY 10-5 10 5 7 0.015 0.060 0.578 261
TRAY 10-7 10 7 7 0.015 0.060 0.628 352
TRAY 10-9 10 9 7 0.015 0.060 0.732 445
TRAY 10-12 10 12 7 0.015 0.080 0.861 610
TRAY 10-19 10 19 7 0.015 0.080 1.020 1060