Two Conductor XLPE/PVC/AIA/PVC Armored Control Cable (1000 V)

CSA TECK90 Armored Control Cable (1000 V)

XLPE/PVC/AIA/PVC Two Conductor Armored Control and Power Cable
1000 V, CSA TECK90

Product Approvals:

  • CSA Standard C22.2 No. 131 and No. 174
  • CSA Approval number: LR1781
  • CSA FT1 and FT4
  • IEEE 383 (70,000 BTU/hr)
  • UL 1581 (70,000 BTU/hr
  • IEEE 1202 (70,000 BTU/hr) CSA FT4
  • ICEA T-30-520 (70,000 BTU/hr)
  • Hazardous Location Rating: HL
  • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method
  • OSHA acceptable

Two Conductor TECK90 Armored Control Cable (1000 V) Construction:

  • Conductor:
    • 14 AWG thru 8 AWG bare copper Class B compressed concentric round to ASTM B8
    • 6 AWG thru 1000 kcmil bare copper compact Class B strand
  • Ground (Bonding) Conductor:
    • The conductor consists of one uninsulated stranded bare copper conductor
  • Insulation:
    • Cross-linked Polyethylene (XLPE) Type RW90
    • Color-coded: 14 AWG to 2 AWG-black and white; 1 AWG to 1000 kcmil-printed numbers
  • Inner Jacket:
    • Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
  • Armor:
    • Aluminum Interlocked Armor (AIA)
  • Overall Jacket:
    • ACID-FLAME CHECK flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black

Two Conductor TECK90 Armored Control Cable (1000 V) Applications:

  • For exposed and concealed wiring in dry, damp or wet locations
  • For use in ventilated, non-ventilated and ladder-type cable trays in dry, damp or wet locations
  • For direct earth burial (with protection as required by inspection authority)
  • For wiring in all hazardous locations when used with certified HL cable glands

Two Conductor TECK90 Armored Control Cable (1000 V) Features:

  • Rated at 90°C wet or dry
  • Excellent crush, oil and chemical resistance
  • Provides long service life
  • Meets cold bend and impact tests at -40°C
Part Number AWG SizeNo. of Cond.Nom. Insul. Thick. (in)Nom. O.D. of Cable (in)Approx LBS/MFTArmor (in)Ampacity @ 30°CGround AWG Size
397260-18 14 2 0.045 0.73 219 0.65 15 14
154275-18 12 2 0.045 0.77 255 0.69 20 14
396570-18 10 2 0.045 0.81 291 0.73 30 12
165630-18 8 2 0.045 0.90 392 0.82 45 10
5603.1660415-18 6 2 0.060 1.02 556 0.94 65 8
5644.0202-18 4 2 0.060 1.16 744 1.07 85 8
5644.11015-18 3 2 0.060 1.23 905 1.15 105 6
5644.0201-18 2 2 0.060 1.28 1030 1.20 120 6
5644.01005-18 1 2 0.080 1.42 1235 1.34 140 6
5644.02255-18 1/0 2 0.080 1.53 1425 1.45 155 6
5644.0226-18 2/0 2 0.080 1.58 1660 1.50 185 6
5644.02265-18 3/0 2 0.080 1.69 1995 1.59 210 4
5644.0727-18 4/0 2 0.080 1.79 2350 1.70 235 4
5644.113-18 250 2 0.090 1.93 2779 1.84 265 4
5644.1131-18 350 2 0.090 2.18 3650 2.09 325 3
5644.11325-18 500 2 0.090 2.45 4895 2.33 395 3
5644.1135-18 750 2 0.090 2.79 6872 2.67 500 2
5644.11375-18 1000 2 0.090 3.10 8993 2.98 585 1