Allied Wire and Cable’s TECK90 Armored Control Cable is ideal for use in ventilated, non-ventilated, and ladder-type cable trays for exposed and concealed wiring in dry, damp, or wet locations. This Teck 90 cable is also suitable for direct earth burial applications and wiring in all hazardous locations when used with HL cable glands. It also has an excellent crush, oil, and chemical resistance to ensure long service life and is UL 1581 approved. Typical vertical installations for this armored cable include mine shafts, tall commercial buildings, inlined tunnels, and vertical cable trays.

45 items

600V CSA TECK90 Armored Control Cable Specifications

TECK 90 Armored Cable Construction:

  • Conductor: 14 AWG bare copper, Class B compressed concentric round to ASTM B8
  • Insulation: Cross-linked Polyethylene (XLPE) Type RW90
  • Color-coded: per ICEA Method 4; Individual conductors colored Black with conductor number surface printed in contrasting ink.
  • Ground (Bonding) Conductor: The conductor consists of one uninsulated stranded bare copper conductor
  • Inner Jacket: Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
  • Armor: Aluminum Interlocked Armor (AIA)
  • Overall Jacket: ACID-FLAME CHECK flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
  • Teck 90 Cable Options:
    • Galvanized Steel Interlocked Armor (GSIA)
    • Other constructions available upon request

TECK 90 Armored Cable Ratings and Approvals:

  • Voltage Rating: 600V
  • Max. Temperature: 90°C wet or dry
  • CSA Standard C22.2 No. 131 and No. 174
  • CSA Approval number: LR1781
  • CSA FT1 and FT4
  • IEEE 383 (70,000 BTU/hr)
  • UL 1581 (70,000 BTU/hr)
  • IEEE 1202 (70,000 BTU/hr) CSA FT4
  • ICEA T-30-520 (70,000 BTU/hr)
  • Hazardous Location Rating: HL
  • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method
  • OSHA acceptable
  • Meets cold bend and impact tests at -40°C