Allied Wire and Cable’s 600V CSA TECK90 Armored Power/Control Composite Cable is ideal for use in ventilated, non-ventilated, and ladder-type cable trays for exposed and concealed wiring in dry, damp, or wet locations. This Teck 90 cable is also suitable for direct earth burial applications and wiring in all hazardous locations when used with HL cable glands. It also has an excellent crush, oil, and chemical resistance to ensure long service life and is UL 1581 approved. Typical vertical installations for this armored cable include mine shafts, tall commercial buildings, inlinded tunnels, and vertical cable trays.

11 items

600V CSA TECK90 Armored Power/Control Composite Cable Specifications

Armored Composite Teck90 Cable Construction:

  • Conductor:
    • 12 AWG through 8 AWG bare copper, Class B compressed concentric round to ASTM B8
    • 6 AWG through 4/0 AWG bare copper, compact Class B strand
  • Ground (Bonding) Conductor: stranded bare copper
  • Insulation: Cross-linked Polyethylene (XLPE) Type RW90
    • Color-code 14 AWG to 2 AWG-black, red and blue; 1 AWG to 4/0 AWG-printed numbers
  • Inner Jacket: Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
  • Armor: Aluminum Interlocked Armor (AIA)
  • Overall Jacket: ACID-FLAME CHECK flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black

Armored Composite Teck90 Cable Ratings and Approvals:

  • Voltage Rating: 600V
  • Max. Temperature: 90°C wet or dry
  • CSA Standard C22.2 No. 131 and No. 174
  • CSA Approval number: LR1781
  • CSA FT1 and FT4
  • IEEE 383 (70,000 BTU/hr)
  • UL 1581 (70,000 BTU/hr)
  • IEEE 1202 (70,000 BTU/hr) CSA FT4
  • ICEA T-30-520 (70,000 BTU/hr)
  • Hazardous Location Rating: HL
  • Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method
  • OSHA acceptable
  • Meets cold bend and impact tests at -40°C