add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 

EPR/CPE Power Cable with Copper Tape Shield (5kV and 8kV)

Part Number AWG SizeJacket ThickNom. O.D. (in)Nom. Dia. of Cond.Min. Insul. Dia. (in)Max. Insul. Dia. (in)Approx LBS/MFTAmpacity (Duct in Air)Ampacity (Underground)
85505.60300-18 6 0.060 0.6500 0.17 0.415 0.490 293 93 97
85505.60200-18 4 0.060 0.7000 0.22 0.455 0.535 363 120 125
85505.60100-18 2 0.060 0.7600 0.27 0.510 0.590 469 165 165
85505.60050-18 1 0.060 0.7900 0.31 0.545 0.620 537 190 185
85505.62550-18 1/0 0.060 0.8200 0.34 0.580 0.655 621 215 215
85505.62600-18 2/0 0.060 0.8600 0.38 0.620 0.695 726 255 245
85505.62650-18 3/0 0.080 0.9400 0.43 0.665 0.745 883 290 275
85505.67700-18 4/0 0.080 1.0000 0.48 0.720 0.795 1049 330 315
85505.68000-18 250 0.080 1.0500 0.53 0.770 0.850 1195 365 345
85505.68100-18 350 0.080 1.1400 0.62 0.870 0.945 1555 440 415
85505.68250-18 500 0.080 1.2700 0.74 0.990 1.065 2083 535 500
85505.68500-18 750 0.080 1.4500 0.91 1.170 1.250 2981 655 510
85505.68750-18 1000 0.080 1.6000 1.06 1.330 1.400 3808 755 690

EPR/CPE Power Cable with Copper Tape Shield (5kV and 8kV)
UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils, 5kV and 8kV

Product Approvals:

  • Industry Approvals
    • National Electric Code (NEC)
    • UL 1072
    • ICEA S-93-639/NEMA WC71
    • ICEA S-97-682
    • AEIC CS8
    • UL Listed as Type MV-105 for use in accordance with NEC
    • Sizes 1/0 AWG and larger are listed and marked "Sunlight-Resistant FOR CT USE" in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr)
    • IEEE 1202 (70,000 BTU/hr)/CSA FT4
    • OSHA acceptable
  • Optional Flame Tests
    • ICEA T-29-520 (210,000 BTU/hr)

EPR/CPE Power Cable with Copper Tape Shield (5kV and 8kV) Construction:

  • Conductor:
    • 6 AWG thru 1000 kcmil annealed bare copper Class B strand
  • Extended Strand Shield (ESS):
    • Extruded Thermoset Semi-Conducting Stress Control Layer over conductor
  • Insulation:
    • Ethylene Propylene Rubber (EPR) colored to contrast with black conducting shield layers
  • Extruded Insulation Shield (EIS)
    • Thermoset Semi-Conducting Polymeric Layer free stripping from insulation
  • Metallic Shield
    • 5 mil annealed copper tape with an overlap of 25%
  • Jacket:
    • Flame retardant, moisture and sunlight resistant Chlorinated Polyethylene (CPE)

EPR/CPE Power Cable with Copper Tape Shield (5kV and 8kV) Options:

  • PVC jacket
  • Flame Retardant, Chlorinated Polyethylene (CPE) jacket
  • Low-Smoke, Zero-Halogen (LSZH) jacket
  • STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-610

EPR/CPE Power Cable with Copper Tape Shield (5kV and 8kV) Applications:

  • Superior performance in petrochemical plants, pulp and paper mills, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines, utility power generating stations and other industrial three-phrase applications
  • Suitable for use in wet or dry locations, when installed in accordance with NEC
  • For use in aerial, conduit, open tray and underground duct installations
  • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

EPR/CPE Power Cable with Copper Tape Shield (5kV and 8kV) Features:

  • Rated at 105°C
  • Excellent heat and moisture resistance
  • Excellent flame resistance
  • Outstanding corona resistance
  • Flexibility for easy handling
  • High dielectric strength
  • Low moisture absorption
  • Electrical stability under stress
  • Low dielectric loss
  • Chemical resistant
  • Meets cold bend test at -35°C

 

<