add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 

EPR/CPE Power Cable with Copper Wire Shield (5kV and 8kV)

Part Number AWG SizeNom. O.D. (in)Nom. Dia. of Cond.Min. Insul. Dia. (in)Max. Insul. Dia. (in)Approx LBS/MFTAmpacity (Duct in Air)Ampacity (Underground)
95505.325100-18 2 0.7100 0.27 0.510 0.590 404 165 165
95505.327550-18 1/0 0.7800 0.34 0.580 0.655 555 215 215
95505.332600-18 2/0 0.8300 0.38 0.620 0.695 666 255 245
95505.332650-18 3/0 0.8800 0.43 0.665 0.745 791 290 275
95505.332700-18 4/0 0.9300 0.48 0.720 0.795 951 330 315
95505.338000-18 250 1.0100 0.53 0.770 0.850 1112 365 345
95505.338100-18 350 1.1100 0.62 0.870 0.945 1463 440 415
95505.343250-18 500 1.2400 0.74 0.990 1.065 2003 535 500
95505.343500-18 750 1.4400 0.91 1.170 1.250 2875 655 610
95505.333750-18 1000 1.6100 1.06 1.320 1.400 3746 755 690

EPR/CPE Power Cable with Copper Wire Shield (5kV and 8kV)
UL Type MV-105, 133% / 100% Ins. Levels, 115 Mils, 5kV and 8kV

Product Approvals:

  • National Electric Code (NEC)
  • UL 1072
  • ICEA S-93-639/NEMA WC71
  • ICEA S-97-682
  • AEIC CS8
  • UL Listed as Type MV-105 for use in accordance with NEC
  • Sizes 1/0 AWG and larger are listed and marked "Sunlight-Resistant FOR CT USE" in accordance with NEC and also meet IEEE 383 (70,000 BTU/hr)
  • IEEE 1202 (70,000 BTU/hr)/CSA FT4
  • Meets EPA 40 CFR part 261 leachable lead content per TCLP method
  • OSHA acceptable

EPR/CPE Power Cable with Copper Wire Shield (5kV and 8kV) Construction:

  • Conductor:
    • 2 AWG thru 1000 kcmil annealed bare copper Class B strand
  • Extended Strand Shield (ESS):
    • Extruded Thermoset Semi-Conducting Stress Control Layer over conductor
  • Insulation:
    • Ethylene Propylene Rubber (EPR) colored to contrast with black jacket material
  • Composite Insulation Shield and Jacket:
    • Six corrugated copper drain wires embedded in composite layers of Semi-Conducting Thermoset Copolymer and Semi-Conducting Black Flame Retardant Chlorinated Polyethylene (CPE)

EPR/CPE Power Cable with Copper Wire Shield (5kV and 8kV) Applications:

  • Installed in a broad range of commercial, industrial and utility projects such as pulp and paper mills, petrochemical plants, steel mills, textile mills, water and sewage treatment facilities, environmental protection systems, railroads, mines and fossil fuel utility generating stations
  • Suitable for use in wet or dry locations, when installed in accordance with NEC
  • For use in aerial, conduit, open tray and underground duct installations
  • For use in direct burial if installed in a system with a ground conductor that is in close proximity, and conforms with NEC 250.4 (A) (5)

EPR/CPE Power Cable with Copper Wire Shield (5kV and 8kV) Features:

  • Rated at 105°C
  • Reduced conductor size and shield system provides the smallest premium medium-voltage shielded power cable with full insulation
  • Smaller outside dimensions reduce the size of duct needed or increase the ampacity per duct
  • All features contribute to faster and easier installation
  • Superior cold bend and cold impact performance
  • Stable and constant shield short circuit performance
  • Excellent heat and moisture resistance
  • Outstanding corona resistance
  • Flexibility for easy handling
  • High dielectric strength
  • Low dielectric loss
  • Low moisture absorption
  • Electrical stability under stress
  • Chemical and radiation resistant
  • Sunlight resistant
  • Meets cold bend test at -55°C