EPR Power Cable with Overall CPE Jacket and Copper Tape Shield (5kV and 8kV)

Part Number AWG SizeGround AWG SizeJacket ThickNom. O.D. (in)Nom. Dia. of Cond.Min. Insul. Dia. (in)Max. Insul. Dia. (in)Approx LBS/MFTAmpacity (Duct in Air)Ampacity (Underground)
77965.200300-18 6 6 0.080 1.2900 0.17 0.415 0.490 939 92 95
77965.200200-18 4 6 0.080 1.3900 0.22 0.455 0.535 1158 120 125
77965.200100-18 2 6 0.080 1.5100 0.27 0.510 0.590 1511 165 160
77965.202550-18 1/0 4 0.080 1.6700 0.34 0.580 0.655 2030 215 210
77965.202600-18 2/0 4 0.080 1.8200 0.38 0.620 0.695 2449 245 235
77965.202700-18 4/0 3 0.110 2.0700 0.48 0.720 0.795 3438 320 305
77965.203000-18 250 2 0.110 2.1500 0.53 0.770 0.850 3968 350 335
77965.203100-18 350 2 0.110 2.3600 0.62 0.870 0.945 5009 430 400
77965.203250-18 500 1 0.110 2.6400 0.74 0.990 1.065 6793 525 485
77965.203500-18 750 1/0 0.140 3.14 0.91 1.170 1.250 9833 635 585
77965.203750-18 1000 2/0 0.140 3.48 1.06 1.330 1.400 12601 725 660

EPR Power Cable with Overall CPE Jacket and Copper Tape Shield (5kV and 8kV)
UL Type MV105, 133% / 100% Ins. Levels, 115 Mils, Three Conductor, 5kV and 8kV

Product Approvals:

  • Industry Approvals:
    • National Electric Code (NEC)
    • UL 1072
    • ICEA S-93-639/NEMA WC74
    • ICEA S-97-682
    • AEIC CS8
    • UL Listed as Type MV-105 for use in accordance with NEC
    • UL 1685 (70,000 BTU/hr)
    • OSHA acceptable
  • Optional Flame Tests:
    • IEEE 1202 (70,000 BTU/hr)/CSA FT4
    • ICEA T-29-520 (210,000 BTU/hr)

EPR Power Cable with Overall CPE Jacket and Copper Tape Shield (5kV and 8kV) Construction:

  • Conductor:
    • 6 AWG thru 1000 kcmil annealed bare copper compact Class B strand
  • Extended Strand Shield (ESS):
    • Extruded Thermoset Semi-Conducting Stress Control Layer over conductor
  • Insulation:
    • Ethylene Propylene Rubber (EPR) insulation, colored to contrast with the black conducting shield layers
  • Extruded Insulation Shield (EIS):
    • Thermoset Semi-Conducting Polymeric Layer free stripping from insulation
  • Metallic Shield:
    • 5mil annealed copper tape with an overlap of 25%
  • Grounding Conductor:
    • 1 bare grounding conductor may be in contact with metallic shielding tape
  • Overall Jacket:
    • Flame retardant, moisture and sunlight resistant Chlorinated Polyethylene (CPE)

EPR Power Cable with Overall CPE Jacket and Copper Tape Shield (5kV and 8kV) Options:

  • PVC jacket
  • Flame Retardant, Chlorinated Polyehtylene (CPE) jacket
  • Low-Smoke, Zero-Halogen (LSZH) jacket
  • Jacketed singles
  • UniShield singles
  • STRANDFILL® - blocked conductor. Tested in accordance with ICEA T-31-610
  • 3 bare copper ground wires
  • Covered ground wires

EPR Power Cable with Overall CPE Jacket and Copper Tape Shield (5kV and 8kV) Applications:

  • Suited for use in a broad range of commercial, industrial and utility applications, where reliability is the major concern, space is limited and ease of installation is critical
  • In wet or dry locations, when installed in accordance with NEC
  • For use in aerial, direct burial, conduit, open tray and underground duct installations

EPR Power Cable with Overall CPE Jacket and Copper Tape Shield (5kV and 8kV) Features:

  • Rated at 105°C
  • Excellent heat and moisture resistance
  • Outstanding corona resistance
  • Flexibility for easy handling
  • High dielectric strength
  • Low moisture absorption
  • Electrical stability under stress
  • Low dielectric loss
  • Chemical resistant
  • Meets cold bend test at -35°C