PVC/PVC Instrumentation Cable with Individual and Overall Shielded Pairs

Part Number AWG SizeConductor StrandingApprox LBS/MFTNo. of PairsNom. Insul. Thick. (in)Jacket ThickNom. O.D. of Cable (in)
162965-18 20 7/.0121 46 2 .012 .040 .316
162975-18 20 7/.0121 76 4 .012 .042 .325
169875-18 20 7/.0121 148 8 .012 .050 .426
169880-18 20 7/.0121 223 12 .012 .060 .640
174055-18 20 7/.0121 280 16 .012 .060 .705
169885-18 20 7/.0121 339 20 .012 .060 .780
169890-18 20 7/.0121 397 24 .012 .060 .845
174060-18 20 7/.0121 586 36 .012 .070 1.015
170895-18 20 7/.0121 786 50 .012 .070 1.190
162930-18 18 7/.0152 61 2 .015 .042 .296
162945-18 18 7/.0152 100 4 .015 .042 .410
174030-18 18 7/.0152 212 8 .015 .060 .485
174035-18 18 7/.0152 315 12 .015 .060 .760
380210-18 18 7/.0152 401 16 .015 .060 .845
169900-18 18 7/.0152 505 20 .015 .070 .955
169905-18 18 7/.0152 596 24 .015 .070 1.040
169910-18 18 7/.0152 846 36 .015 .070 1.215
169915-18 18 7/.0152 1165 50 .015 .080 1.450
162900-18 16 7/.0192 80 2 .015 .042 .346
162910-18 16 7/.0192 151 4 .015 .053 .506
149440-18 16 7/.0192 288 8 .015 .060 .665
149445-18 16 7/.0192 435 12 .015 .060 .855
379885-18 16 7/.0192 575 16 .015 .070 .970
169920-18 16 7/.0192 705 20 .015 .070 1.080
379890-18 16 7/.0192 828 24 .015 .070 1.165
169925-18 16 7/.0192 1215 36 .015 .080 1.390
169930-18 16 7/.0192 1670 50 .015 .090 1.655

PVC/PVC Instrumentation Cable with Individual and Overall Shielded Pairs
UL Type PLTC/ITC, 300 V

Instrumentation Tray Cable Approvals:

  • Industry Compliances:
    • UL 13 Type PLTC/ITC
  • Flame Tests Compliances:
    • IEEE 383 (70,000 BTU/hr)
    • UL Subject 13 (70,000 BTU/hr) for PLTC
    • UL Subject 2250 (70,000 BTU/hr) for ITC
  • Other Compliances:
    • Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
    • OSHA acceptable

Instrumentation Tray Cable Construction:

  • Conductor:
    • 20 AWG thru 16 AWG bare, annealed copper per ASTM B3
    • Class B stranding per ASTM B8
  • Insulation:
    • Polyvinylchloride (PVC)
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
  • Shield:
    • Individual and overall shielded pairs
    • Individual pairs are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Sunlight-resistant Polyvinylchloride (PVC)
  • Options:
    • Tinned copper conductor
    • Class C Stranding
    • Other constructions available upon request

Instrumentation Tray Cable Applications:

  • Acceptable for use in free air or raceways in accordance with NEC
  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • In ducts, cable trays or conduit
  • In accordance with UL Subject 13 as Power-Limited Circuit Cable
  • In class 3 circuits in accordance with NEC
  • In accordance with UL Subject 2250 as Instrumentation Tray Cable (ITC)
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC Article 501-4(b) for UL Type PLTC/ITC cables
  • Per NEC Article 727 for Type PLTC/ITC