Aluminum Jacketed Triplex Conductor Underground Power Cable

More Low Voltage Underground Power Cable Options

Part Number Phase Cond. - AWG SizePhase Cond.- Cond. Strand. Phase Cond. - Nom. Insul. Thick. (in)Phase Cond. - Jacket Thick. (in)Neutral Cond. - AWG Size Neutral Cond. - Cond. Strand.Neutral Cond. - Nom. Insul. Thick. (in)Neutral Cond - Jacket Thick. (in)Nom. EFF O.D. (in)Approx LBS/MFTAmpacity (Direct Burial)Ampacity (Duct in Air)
Vassar/AR/EYS 4 7 0.030 0.030 4 7 0.030 0.030 0.77 204 145 85
Stephens/AR/EYS 2 7 0.030 0.030 4 7 0.030 0.030 0.85 264 185 110
Ramapo/AR/EYS 2 7 0.030 0.030 2 7 0.030 0.030 0.89 294 185 110
Grossmont/AR/EYS 1 19 0.040 0.040 1 19 0.040 0.040 1.06 385 210 130
Brenau/AR/EYS 1/0 19 0.040 0.040 2 7 0.030 0.030 1.07 406 240 150
Bergen/AR/EYS 1/0 19 0.040 0.040 1/0 19 0.040 0.040 1.15 462 240 150
Converse/AR/EYS 2/0 19 0.040 0.040 1 19 0.040 0.040 1.19 499 270 170
Hunter/AR/EYS 2/0 19 0.040 0.040 1 19 0.040 0.040 1.24 557 270 170
Hollins/AR/EYS 3/0 19 0.040 0.040 1/0 19 0.040 0.040 1.29 604 310 195
Rockland/AR/EYS 3/0 19 0.040 0.040 3/0 19 0.040 0.040 1.35 675 310 195
Sweetbriar/AR/EYS 4/0 19 0.040 0.040 2/0 19 0.040 0.040 1.39 732 350 225
Monmouth/AR/EYS 4/0 19 0.040 0.040 4/0 19 0.040 0.040 1.47 821 350 225
Pratt/AR/EYS 250 37 0.045 0.050 3/0 19 0.040 0.040 1.54 886 380 250
Yeshiva/AR/EYS 250 37 0.045 0.050 250 37 0.045 0.050 1.63 992 380 250
Wesleyan/AR/EYS 350 37 0.045 0.050 4/0 19 0.040 0.040 1.73 1155 460 310
Newark/AR/EYS 350 37 0.045 0.050 350 37 0.045 0.050 1.86 1324 460 310
Rider/AR/EYS 500 37 0.045 0.050 350 37 0.045 0.050 2.04 1646 560 380
Aluminum Jacketed Triplex Conductor Underground Power Cable
600V XLPE Insulation & HDXLPE Jacket

Aluminum Jacketed Triplex Conductor Underground Power Cable Construction:

  • Complete Cable:
    • Two phase conductors and one neutral conductor insulated with Extruded Cross-Linked Polyethylene (XLPE) and jacketed with Extruded High-Density Cross-Linked Polyethylene (HDXLPE)
    • Twisted cables form triplex assembly
    • Manufactured in accordance with ANSI/ICEA Standard S-81-570
    • When specified, produced in accordance with UL 854 and listed as a Type USE-2 cable
  • Conductors:
    • Class B compressed aluminum 1350-H19 meeting ASTM B231 or 786
  • Insulation & Jacket:
    • Insulation is XLPE
    • Jacket is HDXLPE and meets ASTM D1248, Type III
    • Phase conductors are black and neutral conductor is black with three extruded yellow stripes.

Aluminum Jacketed Triplex Conductor Underground Power Cable Features:

  • Insulation/Jacket provide very high degree of protection against damage from unclean backfill material, cuts, and abrasions
  • For NEC-compliance, maximum conductor operating temp is 90°C wet or dry
  • Suitable for non-code-compliance with temperature of 90°C wet or dry in accordance with ICEA specifications

Aluminum Jacketed Triplex Conductor Underground Power Cable Applications:

  • Underground systems operated at 600V or less.

Aluminum Jacketed Triplex Conductor Underground Power Cable Options:

  • Aluminum 1350-H16 conductor
  • Copper conductors
  • Other neutral identification methods
  • Sizes 250-500 kcmil available with UL-allowed thin wall (0.080") insulation
  • CDC Combined Duct & Cable
  • Reeless Package
  • PE Insulated/HDPE Jacketed rated 75°C, Type UD-S
  • Type USE-2 per UL 44