XLPE/PVC/AIA/PVC Multi Conductor Armored Control Cable
600 V, CSA TECK90
Product Approvals:
-
CSA Standard C22.2 No. 131 and No. 174
-
CSA Approval number: LR1781
-
CSA FT1 and FT4
-
IEEE 383 (70,000 BTU/hr)
-
UL 1581 (70,000 BTU/hr
-
IEEE 1202 (70,000 BTU/hr) CSA FT4
-
ICEA T-30-520 (70,000 BTU/hr)
-
Hazardous Location Rating: HL
-
Meets EPA 40 CFR, part 261 for leachable lead content per TCLP method
-
OSHA acceptable
CSA TECK90 Armored Control Cable (600 V) Construction:
-
Conductor:
14 AWG bare copper Class B compressed concentric round to ASTM B8
-
Insulation:
Cross-linked Polyethylene (XLPE) Type RW90
-
Color-coded: per ICEA Method 4; Individual conductors colored Black with conductor number surface printed in contrasting ink.
-
Ground (Bonding) Conductor:
The conductor consists of one uninsulated stranded bare copper conductor
-
Inner Jacket:
Flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
-
Armor:
Aluminum Interlocked Armor (AIA)
-
Overall Jacket:
ACID-FLAME CHECK flame retardant, moisture and sunlight resistant Polyvinyl Chloride (PVC)-Black
-
Options:
-
Galvanized Steel Interlocked Armor (GSIA)
-
Other constructions available upon request
CSA TECK90 Armored Control Cable (600 V) Applications:
-
For exposed and concealed wiring in dry, damp or wet locations
-
For use in ventilated, non-ventilated and ladder-type cable trays in dry, damp or wet locations
-
For direct earth burial (with protection as required by inspection authority)
-
For wiring in all hazardous locations when used with certified HL cable glands
CSA TECK90 Armored Control Cable (600 V) Characteristics:
-
Rated at 90°C wet or dry
-
Excellent crush, oil and chemical resistance
-
Provides long service life
-
Meets cold bend and impact tests at -40°C