Ampacities and Correction Factors

Introduction

Establishing ampacity ratings is an inexact procedure. For any given situation, these tables should only be used as a starting point when establishing ratings. Values may be greater than or less than those given in the tables because of the influence of installation method, environment, number of conductors, conductor composition and size, ambient temperatures, insulation types, etc. It is recommended that design engineers desiring accurate ampacity data closely study the 1999 National Electrical Code, Articles 310-15 through 310-84. Additional information can be derived from AIEE, Paper Number 57-660: "The Calculation of the Temperature Rise and Load Capability of Cable Systems" by J.H. Neher and M. H. McGrath. This paper was presented to the AIEE general meeting in Montreal, Quebec, Canada on June 24-28, 1957, and was published in the "AIEE Transactions," Part 3 (power apparatus and systems), Volume 76, October 1957, pp. 752- 772. That information is still applicable. The following tables are to be used in series to determine a wire's ampacity in a given application. Section 6 should be used as a reference for examples of applications of these tables.

Base Ampacities

ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS RATED - THROUGH 2000 VOLTS, 60°C TO 90°C (140°F TO 194°F) NOT MORE THAN THREE CURRENT-CARRYING CONDUCTORS IN RACEWAY OR CABLE OR EARTH (DIRECTLY BURIED), BASED ON AMBIENT TEMPERATURES OF 40°C (104°F)

AWG105°C
BC, TCC
200°C
BC, TCC,
SCC, or NCC
2%-10%
250°C
NCC 2%-10%
250 °C
"A" Nickel
450°C
NCC-Class
27
450°C
"A" Nickel
246.67.28494.3
2299.610.85125.6
201314157188
181718209.42311
16222426123014
14343639184521
12434554255626
10556073347535
87683934310449
6961101175513865
41201251486916276
31431521667818285
21601711919021099
1186197215101236110
1/0215229244114268126
2/0251260273128300141
3/0288297308166338159
4/0332346361169397186
250365385398187----
300414436452212----
350461486503236----
400495522540254----
500563593613288----


Temperature Correction Factors

CORRECTION FACTORS FOR AMBIENT TEMPERATURES OTHER THAN 40°C (104°F),
MULTIPLY THE AMPACITIES BY THE APPROPRIATE FACTOR SHOWN BELOW

Ambient
Temp °C
105 °C200 °C250 °C450 °CAmbient
Temp °F
41-500.950.970.980.99106-122
51-600.900.940.950.99124-140
61-700.850.900.930.96142-158
71-800.800.870.900.95160-176
81-900.740.830.870.93177-194
91-1000.670.790.850.92195-212
101-1200.520.710.790.89213-248
121-1400.300.610.720.86249-284
141-160--0.500.650.84285-320
161-180--0.350.580.81321-356
181-200----0.490.78357-392
201-225----0.350.74393-437
226-250------0.69439-482
251-275------0.65483-527
276-300------0.60528-572
301-325------0.55573-617
326-350------0.49618-662
351-375------0.42663-707
376-400------0.34708-752
401-450--------753-842

ADJUSTMENT FACTORS FOR MORE THAN THREE CURRENT-CARRYING CONDUCTORS IN A RACEWAY OR CABLE
(NEC Table 310-15 (b)(2)(a))

Number of Current-Carrying
Conductors
Percent of Values as Adjusted
for Ambient Temperature if Necessary
4-680
7-970
10-2050
21-3045
31-4040
41 and above35


Suggested Ampacities and Conversions

All types of insulations - Based on National Electric Code

CopperAluminum
No more than 3 conductors in raceway or cableSingle conductor in free airNo more than 3 conductors in raceway or cableSingle conductor in free air
Conductor Temperature RatingConductor Temperature Rating
Size
AWG
or
MCM
85-90°C
TEMP
185F
110°C
TEMP
230F
85-90°C
TEMP
185F
110°C
TEMP
230F
125°C
TEMP
257F
200°C
TEMP
392F
85-90°C
TEMP
185F
110°C
TEMP
230F
85-90°C
TEMP
185F
110°C
TEMP
230F
125°C
TEMP
257F
200°C
TEMP
392F
14253030404045------------
12303540505055252530404045
10404555657075303545505560
85560758590100404555657080
6708010012012513555608095100105
4951051351601701807580105125135140
2125135185210225240100105140165175185
1145160215245265280110125165190205220
0165190250285305325130150190220240255
1/0190215290330355370145170220255275290
2/0215245335385410430170195255300320335
3/0250275390445475510195220300345370400
4/0275315440495530--220250330385415--
300310345485555590--250275375435460--
350340390550610655--270310415475510--
400365420595665710--295335450520555--
500415470675765815--335380515595635--
600460525750855910--370425585675720--
7005005608259401005--405455646745795--
7505155808559801045--420470670775825--
80053560088510201085--430485695805855--
900565--950------465--750------
1000590680102011651240--485560800930990--


Correction Factors for Various Ambient Temperatures*

40°C0.90.940.90.90.95--0.90.940.90.940.95--
50°C0.80.870.80.870.89--0.80.870.80.870.89--
60°C0.670.790.670.790.830.910.670.790.670.790.830.91
70°C0.520.710.520.710.760.870.520.710.520.710.760.87
80°C0.30.610.30.610.710.840.30.610.30.610.710.84
90°C--0.5--0.50.610.81--0.5--0.50.610.81
100°C--------0.510.77--------0.510.77
120°C----------0.69----------0.69
140°C----------0.59----------0.59

*Based on ambient temperature of 30°C (85°F)