5301UE - Instrumentation Cable (18 AWG, 300V)

Belden 5301UE is a instrumentation cable designed for industrial instrumentation and control applications.

This cable features 3 conductors of 18 AWG, 7-strand bare copper conductors. Rated for 300V, the cable uses Polypropylene (PP) insulation and a Polyvinylchloride (PVC) jacket, with insulation thickness of 0.008 inches. The cable operates up to 75C and is approved to NEC Type CMR standards. Approximate weight is 22 lbs/MFT with Black/Red/White color coding.

To explore additional configurations and related part numbers, browse the full Belden cable product line.

Contact Allied Wire & Cable for pricing, availability, and technical support.

Frequently Asked Questions

What is the conductor size of Belden 5301UE?

Belden 5301UE features 18 AWG conductors.

What is the voltage rating of Belden 5301UE?

This cable is rated for 300 volts.

What NEC type is Belden 5301UE?

Belden 5301UE is rated NEC Type CMR.

5301UE

Part Number

5301UE

Attributes

No. of Cond.

3

Approx LBS/MFT

22.00

AWG Size

18

Color Code Chart

Black, Red, White

Cond. Material

Bare Copper

Conductor Stranding

7/26

Insul. Material

Polypropylene (PP)

Jacket Material

Polyvinylchloride (PVC)

Jacket Thickness

0.017

Max. Temp

75C

NEC Type

CMR

No. of Strands

7

Nom. Insul. Thick. (in)

0.008

Nom. O.D. of Cable (in)

0.167

Strand Size

26

Voltage

300