22673 - Instrumentation Cable (20 AWG, 16-Triad, 300V)
Belden 22673 is a instrumentation cable designed for industrial instrumentation and control applications.
This cable contains 16 triads of 20 AWG, 7-strand tinned copper conductors with individually foil shielded pairs and an overall Beldfoil/Polyester Isolation Tape/Beldfoil shield. Rated for 300V, the cable uses Polyvinylchloride (PVC) insulation and a Polyvinylchloride (PVC) jacket, with 0.08-inch jacket thickness and nominal outside diameter of 0.91 inches. The cable operates from -40C to 105C and is approved to CSA Type CIC standards. Approximate weight is 1000 lbs/MFT with Black/White/Red color coding.
To explore additional configurations and related part numbers, browse the full Belden cable product line.
Contact Allied Wire & Cable for pricing, availability, and technical support.
Frequently Asked Questions
What is the conductor configuration of Belden 22673?
Belden 22673 features 16 triads of 20 AWG conductors.
What is the voltage rating of Belden 22673?
This cable is rated for 300 volts.
What shielding does Belden 22673 use?
Belden 22673 has individual foil shields on each pair plus an overall Beldfoil/Polyester Isolation Tape/Beldfoil shield.
What is the temperature rating for Belden 22673?
Belden 22673 is rated for operation up to 105C.
22673
Part Number
22673
Attributes
1000
20
Black, White, Red
Tinned Copper
7/28
CIC
Polyvinylchloride (PVC)
Polyvinylchloride (PVC)
0.080
105C
-40C
7
16
0.9100
Individually Foil and Tape Shielded, Overall Foil Shield
100%
Beldfoil/Polyester Isolation Tape/Beldfoil
28
300