23516 - Instrumentation Cable (18 AWG, 2-Triad, 300V)
Belden 23516 is a instrumentation cable designed for industrial instrumentation and control applications.
This cable contains 2 triads of 18 AWG, 7-strand tinned copper conductors with individually foil shielded pairs and an overall Beldfoil/Polyester Isolation Tape/Beldfoil shield. Rated for 300V, the cable uses Polyvinylchloride (PVC) insulation and a Polyvinylchloride (PVC) jacket, with 0.81-inch jacket thickness and insulation thickness of 0.025 inches. The cable operates from -40C to 105C and is approved to CSA Type ACIC standards. Approximate weight is 275 lbs/MFT with Black/White/Red color coding.
To explore additional configurations and related part numbers, browse the full Belden cable product line.
Contact Allied Wire & Cable for pricing, availability, and technical support.
Frequently Asked Questions
What is the conductor configuration of Belden 23516?
Belden 23516 features 2 triads of 18 AWG conductors.
What is the voltage rating of Belden 23516?
This cable is rated for 300 volts.
What shielding does Belden 23516 use?
Belden 23516 has individual foil shields on each pair plus an overall Beldfoil/Polyester Isolation Tape/Beldfoil shield.
What is the temperature rating for Belden 23516?
Belden 23516 is rated for operation up to 105C.
23516
Part Number
23516
Attributes
275
Aluminum
18
Black, White, Red
Tinned Copper
7/26
ACIC
Polyvinylchloride (PVC)
0.51
Polyvinylchloride (PVC)
0.81
105C
-40C
7
2
0.025
Individually Foil and Tape Shielded, Overall Foil Shield
100%
Beldfoil/Polyester Isolation Tape/Beldfoil
26
300