7423AS - Instrumentation Cable (16 AWG, 600V)
Belden 7423AS is a instrumentation cable designed for industrial instrumentation and control applications.
This cable features 4 conductors of 16 AWG, 26-strand bare copper conductors with an overall Tinned Copper Braid shield. Rated for 600V, the cable uses Polyvinylchloride (PVC) insulation and a Polyvinylchloride (PVC)/Oil and Abrasion-Resistant Polyvinylchloride (PVC) jacket, with nominal outside diameter of 0.4 inches. The cable operates from -40C to 90C and is approved to CSA Type AWM I/II A/B standards. Approximate weight is 136 lbs/MFT with Black & Numbered/Green/Yellow Ground color coding.
To explore additional configurations and related part numbers, browse the full Belden cable product line.
Contact Allied Wire & Cable for pricing, availability, and technical support.
Frequently Asked Questions
What is the conductor size of Belden 7423AS?
Belden 7423AS features 16 AWG conductors.
What is the voltage rating of Belden 7423AS?
This cable is rated for 600 volts.
What shielding does Belden 7423AS have?
Belden 7423AS has an overall Tinned Copper Braid shield.
What is the temperature rating for Belden 7423AS?
Belden 7423AS is rated for operation up to 90C.
7423AS
Part Number
7423AS
Attributes
4
136
16
Black & Numbered, Green/Yellow Ground
Bare Copper
26/30
AWM I/II A/B
Polyvinylchloride (PVC)
Polyvinylchloride (PVC)/Oil and Abrasion-Resistant Polyvinylchloride (PVC)
0.035
90C
-40C
26
0.022
0.4000
Overall Braid Shield
85%
Tinned Copper Braid
30
2587
600