88240 - Instrumentation Cable (20 AWG, 300 (UL) and 1400 (Non-UL)V)

Belden 88240 is a instrumentation cable designed for industrial instrumentation and control applications.

This cable features 20 AWG, 1-strand bare copper conductors with an overall Tinned Copper Braid shield. Rated for 300 (UL) and 1400 (Non-UL)V, the cable uses Fluorinated Ethylene Propylene (FEP) Teflon insulation and a Fluorinated Ethylene Propylene (FEP) Teflon jacket, with nominal outside diameter of 0.159 inches. The cable operates from -70C to 200C and is approved to NEC Type CMP standards. Approximate weight is 24 lbs/MFT.

To explore additional configurations and related part numbers, browse the full Belden cable product line.

Contact Allied Wire & Cable for pricing, availability, and technical support.

Frequently Asked Questions

What is the conductor size of Belden 88240?

Belden 88240 features 20 AWG conductors.

What is the voltage rating of Belden 88240?

This cable is rated for 300 (UL) and 1400 (Non-UL) volts.

What shielding does Belden 88240 have?

Belden 88240 has an overall Tinned Copper Braid shield.

What NEC type is Belden 88240?

Belden 88240 is rated NEC Type CMP.

88240

Part Number

88240

Attributes

Approx LBS/MFT

24

AWG Size

20

Cond. Material

Bare Copper

Conductor Stranding

solid

Dielectric (in)

0.107

Dielectric Material

Fluorinated Ethylene Propylene (FEP) Teflon

Jacket Material

Fluorinated Ethylene Propylene (FEP) Teflon

Max. Temp

200C

Min. Temp

-70C

NEC Type

CMP

No. of Strands

1

Nom. Cap. (pF/ft)

26.4

Nom. DCR of Cond.

10.2O/M'

Nom. DCR of Shld.

6.7O/M'

Nom. Dia. of Cond.

0.032

Nom. Imp.

53.5

Nom. O.D. (in)

0.1590

Shield

Overall Braid Shield

Shield Coverage

0.95

Shield Material

Tinned Copper Braid

Voltage

300 (UL) and 1400 (Non-UL)