add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 

VITALink® 2 Hour Circuit Integrity Cable (NEC Type FPLR)

Part Number AWG SizeNo. of Cond.Conductor StrandingNom. O.D. of Cable (in)Approx LBS/MFTNom. Cap. (pF/ft)
COM 35787 14 2 Solid 0.345 76 36
COM 35785 16 2 Solid 0.315 53 21
VITALink Cable - 2 Hour Fire Rated Circuit Integrity Cable
Comtran Cable
FPLR Cable

VITALink Cable 2 Hour Fire Rated CI Cable Construction:

  • Conductor: 14 AWG solid color-coded Bare Copper conductors specially engineered to minimize embrittlement due to fire exposure
  • Insulation: Proprietary Low Smoke Zero Halogen (LSZH) Thermoset Fire-Roc™ Layer
  • Color Code: Black, Red
  • Shield: Copper/Polyester tape applied over core
  • Drain Wire: Stranded Bare Copper
  • Twists per Foot: (Nominal 2.5)
  • Jacket: Low Smoke Zero Halogen (LSZH) Polyolefin (PO) (sequential footage marker provided every two feet)
  • Jacket Color: Red

VITALink Cable 2 Hour Fire Rated FPLR Circuit Integrity Cable Ratings & Approvals:

  • Temperature Rating: 90°C
  • Voltage Rating: 300V
  • UL 1424 Listed FPLR for Power-Limited Fire Alarm Circuits
  • NEC Type FPLR rated for use in Electrical Circuit Integrity System FHIT.40
  • Certified to ANSI/UL 2196 (Tests for Fire Resistive Cables) per UL FHJR.R27557
  • Fire certified for power-limited system use at 50V phase-to-phase utilization voltage
  • UL Listed Type CMR per UL 444
  • UL Listed Type CL3R per UL 13
  • Riser rated per UL 1666
  • Sunlight resistant and wet location rated
  • Low Smoke Zero Halogen
  • California State Fire Marshal Approved

VITALink 2 Hour Fire Rated CI Cable Applications:

  • Comtran's line of VITALink Cable, featuring FPLR Circuit Integrity Cable, is designed for use in a wide range of critical systems, including emergency voice-alarm communication (EVAC), smoke/fire alarm systems, fireman’s telephone and area of refuge communication systems, and visible notification appliances.
  • 2 Hour Fire Rated Cable is ideal for health care facilities, smoke control equipment, elevators, fire pump - feeder/controls, command center critical systems, pressurized stairway systems and smoke management systems.
  • VITALink 2 Hour CI Cable can be installed in manufacturing, commercial and industrial locations along with colleges, high-rise buildings, hotels, airports and stadiums.
  • VITALink 2 Hour Fire Rated Cable is recommended for use in tunnels and subways for emergency communications, electrical equipment rooms - feeders/service, emergency generators and standby power systems.