The FPLR VITALink 2 Hour Circuit Integrity cable by Comtran is rated for riser applications and has passed multiple flame tests. This cable features an inner coating that hardens at high temperatures, preventing damage to the signal of the cable. It has also passed seven two-hour burn tests at 1850°F. This cable features solid bare copper conductors, LSZH insulation, an LSZH jacket, and an overall copper/polyester tape shield. It is suitable for a large variety of emergency communications and fire alarm systems.

2 items

  • COM 35785
    $0.00 / 100 FT
    • Approx LBS/MFT: 53
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • COM 35787
    $0.00 / 100 FT
    • Approx LBS/MFT: 76
    • AWG Size: 14
    • Cond. Material: Bare Copper
    Order
    Add to List

VITALink 2 Hour Fire Rated CI Cable Specifications

VITALink Cable Construction:

  • Conductor: 14 AWG solid color-coded Bare Copper conductors specially engineered to minimize embrittlement due to fire exposure
  • Insulation: Proprietary Low Smoke Zero Halogen (LSZH) Thermoset Fire-Roc™ Layer
  • Color Code: Black, Red
  • Shield: Copper/Polyester tape applied over core
  • Drain Wire: Stranded Bare Copper
  • Twists per Foot: (Nominal 2.5)
  • Jacket: Low Smoke Zero Halogen (LSZH) Polyolefin (PO) (sequential footage marker provided every two feet)
  • Jacket Color: Red

VITALink Cable Ratings and Approvals:

  • Temperature Rating: 90°C
  • Voltage Rating: 300V
  • UL 1424 Listed FPLR for Power-Limited Fire Alarm Circuits
  • NEC Type FPLR rated for use in Electrical Circuit Integrity System FHIT.40
  • Certified to ANSI/UL 2196 (Tests for Fire Resistive Cables) per UL FHJR.R27557
  • Fire certified for power-limited system use at 50V phase-to-phase utilization voltage
  • UL Listed Type CMR per UL 444
  • UL Listed Type CL3R per UL 13
  • Riser rated per UL 1666
  • Sunlight resistant and wet location rated
  • Low Smoke Zero Halogen
  • California State Fire Marshal Approved

VITALink Cable Applications:

  • Comtran's line of VITALink Cable, featuring FPLR Circuit Integrity Cable, is designed for use in a wide range of critical systems, including emergency voice-alarm communication (EVAC), smoke/fire alarm systems, fireman’s telephone and area of refuge communication systems, and visible notification appliances.
  • 2 Hour Fire Rated Cable is ideal for health care facilities, smoke control equipment, elevators, fire pump - feeder/controls, command center critical systems, pressurized stairway systems and smoke management systems.
  • VITALink 2 Hour CI Cable can be installed in manufacturing, commercial and industrial locations along with colleges, high-rise buildings, hotels, airports and stadiums.
  • VITALink 2 Hour Fire Rated Cable is recommended for use in tunnels and subways for emergency communications, electrical equipment rooms - feeders/service, emergency generators and standby power systems.