Home
loading content

Industrial Belden Coaxial Cables

5 items

89907
Approx LBS/MFT24
AWG Size20
Cond. MaterialTinned Copper
Conductor Stranding19/32
Dielectric (in)0.095
Dielectric MaterialFoam Fluorinated Ethylene Propylene (FFEP)
Jacket MaterialPolyvinylidene Fluoride (PVDF)
Max. Temp150C
Requires Quote per FT 
9907
Approx LBS/MFT25
AWG Size20
Cond. MaterialTinned Copper
Conductor Stranding19/32
Dielectric (in)0.102
Dielectric MaterialFoam Polyethylene (FPE)
Jacket MaterialPolyvinylchloride (PVC)
Max. Temp60C
Starting at 1.19 per FT 
89880
Approx LBS/MFT134
AWG Size12
Cond. MaterialBare Copper
Conductor Strandingsolid
Dielectric (in)0.245
Dielectric MaterialFoam Fluorinated Ethylene Propylene (FFEP)
Jacket MaterialPolyvinylidene Fluoride (PVDF)
Max. Temp150C
Requires Quote 
9880
Approx LBS/MFT131
AWG Size12
Cond. MaterialBare Copper
Conductor Strandingsolid
Dielectric (in)0.243
Dielectric MaterialFoam Polyethylene (PE)
Jacket MaterialPolyvinylchloride (PVC)
Max. Temp60C
Requires Quote per FT 
2413
AWG Size23
Cond. MaterialBaer Copper, Bare Copper
Conductor Strandingsolid
CSA TypeFT6
Insul. MaterialPO; FEP - Polyolefin; Fluorinated Ethylene Propylene
Jacket MaterialPVC-LS
No. of Cond.8
No. of Pairs4
Requires Quote 

Belden Industrial Ethernet Coaxial (Thinnet and Thicknet) Cable Specifications

Ethernet Cable Ratings and Approvals:

  • Thinnet Cable:
    • Non-Plenum:
      • UL AWM Style Style 1354 (30V, 60°C)
      • NEC Type CL2, CM
      • CEC Type CM
    • Plenum:
      • RG58U Cable
      • Temperature Rating: 150°C
      • NEC Type CL2P, CMP
      • CEC Type CMP FT6
  • Thicknet Cable:
    • Non-Plenum:
      • UL AWM Style 1478 (30V, 60°C)
      • NEC Type CL2, CM
      • CEC Type CM
    • Plenum:
      • Temperature Rating: 150°C
      • NEC Type CL2P, CMP
      • CEC Type CMP FT6

Ethernet Cable Construction:

  • Conductor:
    • Thinnet: 20 AWG Stranded Tinned Copper
    • Thicknet: 12 AWG Solid Bare Copper
  • Insulation: Foam Polyethylene (non-plenum) or Foam FEP (plenum)
  • Jacket: PVC (non-plenum) or Fluorocopolymer (plenum)
  • Shielding:
    • Thinnet: Duobond II (100% Coverage) and Tinned Copper Braid (93% Coverage)
    • Thicknet: Duobond IV Quad Shield (100% Coverage)