Home
loading content

TelcoFlex III

TelcoFlex III Cable

The TelcoFlex III cable features a single stranded tinned copper conductor, low-smoke and zero-halogen TelcoHyde insulation, and an overall natural cotton braid covering. The braid is finished with a moisture resistant, flame retardant saturant. This cable is available in a range of sizes from 14 AWG to 750 KCMIL. This cable is rated at 600V and has a temperature rating of 60°C for wet conditions and 90°C for dry conditions.

13 items

telco-2/0-l3
Approx LBS/MFT537.00
AWG Size2/0
Cond. MaterialTinned Copper
Conductor Stranding19/.0837
CSA TypeAWM I B
Equals088808
Insul. MaterialHalogen-Free (LSZH) Thermoplastic (TPE)
Insulation Min. Avg. Wall80
Requires Quote 
telco-4/0-l3
Approx LBS/MFT808.00
AWG Size4/0
Cond. MaterialTinned Copper
Conductor Stranding19/.1055
CSA TypeAWM I B
Equals088810
Insul. MaterialHalogen-Free (LSZH) Thermoplastic (TPE)
Insulation Min. Avg. Wall80
Requires Quote per FT 
telco-350-l3
Approx LBS/MFT1290.00
AWG Size350
Cond. MaterialTinned Copper
Conductor Stranding37/.0973
CSA TypeAWM I B
Equals088812
Insul. MaterialHalogen-Free (LSZH) Thermoplastic (TPE)
Insulation Min. Avg. Wall95
Requires Quote per FT 
telco-500-l3
Approx LBS/MFT1796.00
AWG Size500
Cond. MaterialTinned Copper
Conductor Stranding37/.1162
CSA TypeAWM I B
Equals088813
Insul. MaterialHalogen-Free (LSZH) Thermoplastic (TPE)
Insulation Min. Avg. Wall95
Requires Quote per FT 
telco-750-l3
Approx LBS/MFT2629.00
AWG Size750
Cond. MaterialTinned Copper
Conductor Stranding61/.1109
CSA TypeAWM I B
Equals088814
Insul. MaterialHalogen-Free (LSZH) Thermoplastic (TPE)
Insulation Min. Avg. Wall110
Requires Quote per FT 

TelcoFlex III Power Cable Specifications

TelcoFlex III Construction:

  • Conductor: Stranded tinned copper conductor
  • Insulation: Limited smoke, non-halogen TelcoHyde 5221, which features a limiting oxygen rating of 35%
  • Separator: 1 mil clear mylar tape is applied over the insulation for sixes 6 AWG and larger
  • Covering: Overall natural cotton braid. A section of completed cable has a limiting oxygen index of 35%.
  • Finish: Moisture resistant and flame retardant saturant and color finisher are applied to the braid.

TelcoFlex III Ratings and Approvals:

  • Temperature Rating: 90°C Dry and 60°C Wet
  • Voltage Rating: 600V
  • ASTM B-33
  • UL: RHH/LS, Listed for CT Use (Sizes 1/0 AWG and Larger)
  • CSA: AWM / B 105°C
  • FT4-ST1 Flame Test
  • VW-1
  • IEC 60674 and 60332
  • RoHS and Reach Compliant

TelcoFlex is a TM of Southwire Company