TelcoFlex® II Central Office Power Cable

Part Number AWG SizeConductor StrandingInsulation Min. Avg. WallNom. I.D. (in)Max. Resistance @ 20°C OHMS/MFTApprox LBS/MFT
TELCO-8-L2 8 41/.0201 60 0.274 0.6790 78.00
TELCO-6-L2 6 65/.0201 60 0.315 0.4360 122.00
TELCO-4-L2 4 105/.0201 60 0.385 0.2740 186.00
TELCO-2-L2 2 168/.0201 60 0.43 0.1720 256.00
TELCO-1/0-L2 1/0 266/.0201 80 0.56 0.1090 434.00
TELCO-2/0-L2 2/0 342/.0201 80 0.62 0.0868 533.00
TELCO-4/0-L2 4/0 532/.0201 80 0.745 0.0546 832.00
TELCO-350-L2 350 888/.0201 95 0.96 0.0334 1298.00
TELCO-500-L2 500 1221/.0201 95 1.09 0.0234 1810.00
TELCO-750-L2 750 1850/.0201 110 1.314 0.0157 2680.00
TelcoFlex II Central Office Power Cable
Low Smoke, Non-Halogenated Insulation, Lead-Free and Silicone-Free

Class I Flexible Strand with Braid

TelcoFlex II Cable Description:

  • TelcoFlex II Central Office Power Wire and Cable incorporates low smoke zero halogen TelcoHyde insulation. It also includes either a bunched or rope bunched stranded tinned copper conductor, covered with an opaque mylar tape to facilitate stripping.
  • TelcoFlex II Cables are type RHH/LS to be used in accordance with the National Electrical Code.

TelcoFlex II Cable Ratings and Approvals:

  • Temperature Rating: 90°C/105°C Dry and 60°C Wet
  • Voltage Rating: 600V
  • UL: Central Office Power Cable; UL Standard 44 ( Type RHH/ST1 Thermoset Insulated)
  • CT Rated: Sizes 1/0 and larger are UL, CT Use
  • VW-1
  • FT-4 Flame Test
  • ASTM B-33 and B172 for Flexible Strand
  • Listed for CT Use (Sizes 1/0 AWG and Larger)
  • CSA: AWM / B 105°C, 600V
  • Testing: Physical and electrical tests in accordance with UL Standard 44 requirements
  • IEC 60674 and 60332
  • RoHS and Reach Compliant
  • Meets the requirements of WP93811 for Cold Flow (Creep) and Cut through

TelcoFlex II Cable Construction:

  • Conductor: Class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conductor
  • Insulation: 90°C rated limited smoke, non-halogen TelcoHyde 5221, which features a limiting oxygen rating of 35%