34 items
-
$0.00 /
- Approx LBS/MFT: 624
- AWG Size: 14
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 875
- AWG Size: 14
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 139
- AWG Size: 14
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 301
- AWG Size: 14
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 268
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 148
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 124
- AWG Size: 12
- Cond. Material: Tinned Copper
-
$0.00 /
- Approx LBS/MFT: 157
- AWG Size: 12
- Cond. Material: Tinned Copper
FR-EPR/CPE Unshielded Multi-Conductor TC-ER Control Cable (E-2 Color Code) Specifications
FR-EPR/CPE Unshielded TC-ER Control Cable Construction:
- Conductor: 14 AWG through 10 AWG fully annealed stranded tinned copper per ASTM B33; Class B stranding per ASTM B8
- Insulation: Flame Retardant Ethylene Propylene Rubber (FR-EPR) Type II
- Color-coded per ICEA Method 1; Table E-2 (Does not include white or green)
- Jacket: Flame Retardant Thermoplastic Chlorinated Polyethylene (CPE)
- Unshielded Control Cable Options:
- 2kV version
- Bare copper conductor
- Class C stranding
- E-2 Color Code
- Shielded
- Flame Retardant Cross-Linked Polyethylene (FR-XLPE) insulation
- Thermoplastic Low-Smoke, Zero-Halogen (LSZH) jacket
- Other constructions available upon request
FR-EPR/CPE Unshielded TC-ER Control Cable Ratings and Approvals:
- Voltage Rating: 600V
- Max. Temperature: 90°C, wet or dry
- UL 44 Type XHHW-2
- UL 1277 Type TC-ER (three or more conductors)
- UL 1581
- ICEA S-73-532
- ICEA S-95-658/NEMA WC70
- UL 1581 VW-1
- UL 1277 Flame Test
- IEEE 383
- IEEE 1202
- CSA FT4
- ICEA T-29-520
- Meets EPA 40 CFR, Part 261 for leachable lead content per TCLP method
- OSHA acceptable
FR-EPR/CPE Unshielded TC-ER Control Cable Features:
- Ripcord applied to all cables with jacket thickness of 60 mils or less
- Excellent physical, thermal, and electrical properties
- Sunlight and weather resistant
- Excellent moisture resistance
- Outstanding resistance to crush, compression cuts, and heat deformation
- Low coefficient of friction for easy pulling
- Excellent flame-resistance - burns to ash; does not exhibit thermoplastic drip
- Excellent low-temperature cold bend characteristics
- Meets cold bend test at -40°C
- Meets the crush and impact requirements of Type MC cable (three conductors or more)
FR-EPR/CPE Unshielded TC-ER Control Cable Applications:
- In free air, raceways, or direct burial
- In wet or dry locations
- Permitted for Exposed Run 'ER' use in accordance with NEC for 2 AWG and larger
- Permitted for use in Class I Division 2 industrial hazardous locations per NEC