add to cart success
This product has variants and can only be added to the cart by viewing the product details page.
add to cart success
Submit Request Quote
 * Denotes Required Field.
Name:
 *
Company Name:
Phone:
Email:
 *
Message:
Request Quote
 

FR-EPR/CPE Instrumentation Cable with Individual and Overall Shielded Triads

Part Number AWG SizeConductor StrandingNom. O.D. of Cable (in)No. of PairsNom. Insul. Thick. (in)Jacket ThickApprox LBS/MFT
168575-18 18 7/.0152 .560 2 .025 .060 127
159625-18 18 7/.0152 .640 4 .025 .060 201
159630-18 18 7/.0152 .825 8 .025 .080 343
168580-18 18 7/.0152 1.065 12 .025 .080 528
147270-18 18 7/.0152 1.180 16 .025 .080 675
168585-18 18 7/.0152 1.310 20 .025 .080 825
168590-18 18 7/.0152 1.500 24 .025 .080 972
168595-18 18 7/.0152 1.740 36 .025 .080 1470
140475-18 16 7/.0192 .615 2 .025 .060 159
140480-18 16 7/.0192 .705 4 .025 .060 249
140485-18 16 7/.0192 .850 8 .025 .080 472
143705-18 16 7/.0192 1.160 12 .025 .080 683
168600-18 16 7/.0192 1.290 16 .025 .080 879
168605-18 16 7/.0192 1.380 20 .025 .080 1058
168610-18 16 7/.0192 1.615 24 .025 .080 1266
168615-18 16 7/.0192 1.920 36 .025 .110 1918

FR-EPR/CPE Instrumentation Cable with Individual and Overall Shielded Triads
UL Type TC, 600 V

FR-EPR/CPE Instrumentation Cable Product Approvals:

  • Industry Compliances:
    • UL 1277 Type TC
    • UL 1581
    • ICEA S-82-552
  • Flame Tests Compliances:
    • UL 1581 VW-1
    • UL 1277
    • IEEE 383
    • IEEE 1202
    • CSA FT-4
    • ICEA T-29-520
  • Other Compliances:
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA acceptable

FR-EPR/CPE Instrumentation Cable Construction:

  • Conductor:
    • 18 AWG and 16 AWC tinned, annealed copper per ASTM B33
    • Class B stranding per ASTM B8
  • Insulation:
    • Flame retardant Ethylene Propylene Rubber (FR-EPR) Type II
    • Color-coded per ICEA Method 1:
      • Triads: Black, White, and Red
  • Shield:
    • Individual triads are 100% shielded with aluminum/polyester in contact with stranded tinned copper drain wire.
  • Jacket:
    • Flame retardant thermoplastic Chlorinated Polyethylene (CPE)
  • Options:
    • Bare copper conductor
    • Class C Stranding
    • Overall shielded pairs/triads
    • CCTC-Cross-Linked Polyethylene (XLPE) insulation
    • FREP® XL-flame retardant, thermoset Chlorinated Polyethylene (XL-CPE) jacket
    • FREP® II-flame retardant, thermoplastic Low-Smoke, Zero-Halogen (LSZH) Polyolefin jacket
    • FREP® 300V-UL Type PLTC
    • Other constructions available upon request

FR-EPR/CPE Instrumentation Cable Applications:

  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • Acceptable for use in free air or raceways or direct burial
  • In wet or dry locations
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC

FR-EPR/CPE Instrumentation Cable Features:

  • Rated at 90°C wet or dry
  • Ripcord applied to all cables with jacket thickness of 60 mils or less
  • Sunlight and weather resistant
  • Excellent electrical, thermal, and physical properties
  • Excellent moisture resistance
  • Excellent resistance to compression cuts and heat deformation
  • Excellent flame resistance-burns to an ash; does not exhibit thermoplastic drip
  • Low coefficient of friction for easy pulling
  • "Heavy duty" rating per ICEA standards
  • Excellent low temperature cold bend characteristics
  • Meets cold bend test at -40°C