FR-EPR/CPE, Instrumentation Cable with Overall Shielded Pairs/Triads

Part Number AWG SizeConductor StrandingNo. of PairsNo. of TriadsNom. Insul. Thick. (in)Nom. O.D. of Cable (in)Approx LBS/MFTJacket Thick
143825-18 18 7/.0152 1 .025 .300 42 .045
162625-18 18 7/.0152 1 .025 .315 53 .045
168505-18 18 7/.0152 2 .025 .420 75 .045
168510-18 18 7/.0152 4 .025 .490 117 .045
168515-18 18 7/.0152 8 .025 .675 224 .060
168520-18 18 7/.0152 12 .025 .775 305 .060
147290-18 18 7/.0152 16 .025 .925 425 .080
168525-18 18 7/.0152 20 .025 1.025 510 .080
168530-18 18 7/.0152 24 .025 1.105 604 .080
168535-18 18 7/.0152 36 .025 1.360 865 .080
168540-18 18 7/.0152 50 .025 1.555 1144 .080
157480-18 16 7/.0192 1 .025 .320 52 .045
139845-18 16 7/.0192 1 .025 .335 66 .045
141585-18 16 7/.0192 2 .025 .460 95 .045
141590-18 16 7/.0192 4 .025 .560 171 .060
168545-18 16 7/.0192 8 .025 .740 294 .060
141595-18 16 7/.0192 12 .025 .900 438 .080
168550-18 16 7/.0192 16 .025 1.015 560 .080
168555-18 16 7/.0192 20 .025 1.130 680 .080
168560-18 16 7/.0192 24 .025 1.215 807 .080
168565-18 16 7/.0192 36 .025 1.505 1160 .080
168570-18 16 7/.0192 50 .025 2.095 1702 .080

FR-EPR/CPE Instrumentation Cable with Overall Shielded Pairs/Triads
UL Type TC, 600 V

FR-EPR/CPE Instrumentation Cable Product Approvals:

  • Industry Compliances:
    • UL 1277 Type TC
    • UL 1581
    • ICEA S-82-552
  • Flame Tests Compliances:
    • UL 1581 VW-1
    • UL 1277
    • IEEE 383
    • IEEE 1202
    • CSA FT-4
    • ICEA T-29-520
  • Other Compliances:
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA acceptable

FR-EPR/CPE Instrumentation Cable Construction:

  • Conductor:
    • 18 AWG and 16 AWC tinned, annealed copper per ASTM B33
    • Class B stranding per ASTM B8
  • Insulation:
    • Flame retardant Ethylene Propylene Rubber (FR-EPR) Type II
    • Color-coded per ICEA Method 1:
      • Pairs: Black and White
      • Triads: Black, White and Red
  • Shield:
    • Overall shield is aluminum/polyester in contact with stranded tinned copper drain wire
  • Jacket:
    • Flame retardant thermoplastic Chlorinated Polyethylene (CPE)
  • Options:
    • Bare copper conductor
    • Class C Stranding
    • Individual and Overall shielded pairs/traids
    • CCTC-Cross-Linked Polyethylene (XLPE) insulation
    • FREP® II-flame-retardant, thermoset Chlorinated Polyethylene (XL-CPE) jacket
    • FREP® II-flame-retardant, thermoplastic Low-Smoke, Zero-Halogen (LSZH) Polyolefin jacket
    • FREP® 300V-UL Type PLTC
    • Other constructions available upon request

FR-EPR/CPE Instrumentation Cable Applications:

  • Typical applications include audio, intercom, control, energy management and alarm circuits.
  • Acceptable for use in free air or raceways or direct burial
  • In wet or dry locations
  • Permitted for use in Class 1 Division 2 industrial hazardous locations per NEC

FR-EPR/CPE Instrumentation Cable with Overall Shielded Pairs/Triads Features:

  • Rated at 90°C wet or dry
  • Ripcord applied to all cables with jacket thickness of 60 mils or less
  • Sunlight and weather resistant
  • Excellent electrical, thermal, and physical properties
  • Excellent moisture resistance
  • Excellent resistance to compression cuts and heat deformation
  • Excellent flame resistance-burns to an ash; does not exhibit thermoplastic drip
  • Low coefficient of friction for easy pulling
  • "Heavy duty" rating per ICEA standards
  • Excellent low temperature cold bend characteristics
  • Meets cold bend test at -40°C