The Lapp Control TM CY Cable is suitable for use in machine tools, food and beverage equipment, and processing equipment. This cable features flexible copper stranding, a pressure-extruded jacket, and number-coded conductors for easy connection. It also features a foil tape and braided tinned copper shield that provides 85 percent coverage. This cable is TC-ER approved, meaning it may be installed off the machine and into an overhead tray without conduit.

29 items

  • $0.00 / 1000 FT
    • Approx LBS/MFT: 117.00
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 /
    • Approx LBS/MFT: 128
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 / 1000 FT
    • Approx LBS/MFT: 165.00
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 / 1000 FT
    • Approx LBS/MFT: 287.00
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 / 1000 FT
    • Approx LBS/MFT: 326.00
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 /
    • Approx LBS/MFT: 476
    • AWG Size: 16
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 /
    • Approx LBS/MFT: 121
    • AWG Size: 14
    • Cond. Material: Bare Copper
    Order
    Add to List
  • $0.00 / 1000 FT
    • Approx LBS/MFT: 150.00
    • AWG Size: 14
    • Cond. Material: Bare Copper
    Order
    Add to List

Lapp Control TM CY Cable Specifications

Control TM CY Cable Construction:

  • Conductors: Finely stranded bare copper (Class 5 fine wire)
  • Insulation: Specially blended PVC/Nylon
  • Shielding: Foil tape and tinned copper braid (85% coverage)
  • Color Code: Black with white numbers, plus green/yellow ground
  • Jacket: Specially formulated gray PVC

Control TM CY Cable Ratings and Approvals:

  • Temperature Range:
    • UL/CSA TC: -25°C to +90°C
    • For stationary use: -40 to +105°C
    • For flexible use: -25°C to +90°C
  • Nominal Voltage:
    • UL/CSA TC: 600V
    • UL WTTC: 1000V
  • Test Voltage: 2000V
  • Minimum Bend Radius- Shielded: 6 x cable diameter
  • UL:
    • TC-ER per UL 1277
    • MTW per UL 1063
    • WTTC per UL 2277
    • Bus Drop Cable (14 AWG & larger; 3c & 4c only)
    • AWM 2587 & 21098 (Oil)
  • Attributes:
    • UL Oil Res I/II
    • 75°C Wet; 90°C Dry
    • Sunlight resistant
    • Direct burial
    • NFPA 79 2012
  • NEC: Class 1, Division 2 per NEC Article 501
  • Canada:
    • c(UL) CIC/TC FT4
    • CSA AWM I/II A/B FT4
  • Additional:
    • Torsion rated for wind market (± 90°/m) & (± 150°/m)
    • Passes impact and crush test per UL 1277 (except 20 AWG)
    • CE & RoHS