The Lapp Tray II CY Cable is suitable for use in industrial plant expansions, automotive plants, tray wiring, and anywhere VNTC® cables are used. This shielded cable features an oil-resistant, pressure-extruded PVC jacket for improved flexibility and black numbered conductors for easy identification. It also features a double-laminated foil tape and tinned copper braid shield that provides 70 percent coverage. It is easier to pull than a standard tray cable and is TC-ER approved so no conduit is needed.

31 items

Lapp Tray II CY Cable Specifications

Tray II CY Cable Construction:

  • Conductors: Finely stranded bare copper
  • Insulation: Specially blended PVC/Nylon
  • Color Code: Black with white numbers, plus green/yellow ground
  • Jacket: Specially formulated oil-resistant black PVC
  • Shielding: Double laminated foil tape; tinned copper braid (70% coverage)

Tray II CY Cable Ratings and Approvals:

  • Temperature Range:
    • UL/CSA TC: -25°C to 90°C
    • For stationary use: -40°C to 90°C
    • For flexible use: -5°C to 105°C
  • Nominal Voltage:
    • UL/CSA TC: 600V
    • UL WTTC/CSA AWM: 1000V
  • Minimum Bend Radius for Installation:
    • < 1 AWG: 4 x cable diameter
    • ≥ 1 AWG: 6 x cable diameter
  • UL Approval:
    • TC-ER per UL 1277
    • MTW per UL 1063
    • WTTC per UL 2277
    • PLTC-ER per UL 13 (18-12 AWG)
    • ITC-ER per UL 2250 (18-12 AWG)
    • DP-1 per UL 1690
    • AWM 20886
  • Attributes:
    • UL Oil Res I/II
    • 70°C Wet; 90°C Dry
    • Sunlight Resistant
    • Direct Burial
    • NFPA 79 2012
  • NEC Approval: Class 1 Division 2 per NEC Article 501
  • CSA Approval:
    • CSA AWM I/II A/B FT 4
    • c(UL) CIC/TC FT4
  • Torsion Rated for Wind Market (± 90°/m) and (±150°/m)
  • CE Approved
  • RoHS Compliant
  • MSHA-P07-KA050016-MSHA